Table 6 — Electrical Data (3-Phase, 60-Hz)

f

Shaded

values

are

LRA

drawn

by

first

winding

of

part-winding

start

units

(not

standard

on

38AB054,064,

but may be field modified) See Note 1 Larger value is

total LRA.

FLA — Full Load Amps

ICF

Maximum

Instantaneous

Current

Flow

(sum

of

LRA

of

last compressor to start and FLA of all other motors in
unit, and control circuit current)

LRA

Locked Rotor Amps

MWA

Minimum

Wire

Amps

per

NEC,

Section

430-24

Values

based on maximum of 1% voltage drop in line.

*

*Units

are

suitable

for

use

on

electrical

systems

where

voltage

supplied to the unit terminals is never below or above the listed
limits

tUnits

38AB084

(208-,

230-volt

only) have

two power connections

Maximum wire size is 350 MCM each

NOTES

1

Dual compressor units have a 4- to 12-second delay between

first-

and

second-compressor

start-up

Units

are

supplied

with

either

across-the-line

or

part-winding

start,

depending

on

unit

size and voltage Refer to Electrical Data table Where two LRA
values are shown, units

are part-winding start, (all others are

across-the-line)

2

Units have factory-installed circuit breakers and/or pullout fuses

that

meet

NEC

requirements

for

branch

circuit

over-current

protection and in-sight disconnect Consult local codes

3

Maximum

Incremental

Current

Inrush

during

start-up

is

LRA

drawn by first winding of part-winding start unit (shaded area)
or

across-the-line

LRA

of

largest

compressor

when

part-winding

start is not available

4

Fans no 1 and 4 have single-phase speed control motors on 208-

and 230-volt units

5

Units 38AB054 and 064 which have two contactors, can be

converted

to

part-winding

start

by

addition

of

two

time-delay

relays (Carrier part no FIN67SK001 for 208- and 230-volt units,
or

no

HN67SK002

for

460-and

575-volt

units)

Two

additional

contactors are also required with 460- and 575-volt units to be
wired same as other part-wind compressors

On 38AD024 thru 034 units, power terminal

block is in the control box. Remove the outer

panel and remove the no. 10 screw on the door.
Swing open door, remove screws on barrier panel
and remove barrier panel. On 38AB054,064 and
084 units, remove two screws holding hinged sheet
metal barrier and swing open barrier.

Condenser fans must rotate clockwise when

viewed from above. If necessary, correct direction
of fan rotation by interchanging any two power
input wires at disconnect switch.

Affix crankcase heater decal to unit disconnect

switch.

Control Circuit Wiring —

Internal control voltage

on 38AD units is 115 volts.

Internal control

voltage on 208- and 230-volt 38AB units is the

same as unit voltage. On 460- and 575-volt 38AB
units, it is 115 volts. All control circuit wiring must
comply with applicable local and national codes.
Remote control wiring must enter unit control box
thru control opening (G on Fig. 1) and connect to
terminal block inside the control box.

772