38AB084UNIT

Timers in this unit provide basic function, plus

40 sec bypass for oil failure switch and 1 sec delay
to accomplish part-winding start.

For specific sequence for each unit, refer to

Timing Charts in Fig. 14.

CONTROL
SET POINT
ADJUSTMENT

NUT

PRESSURE

DIFFERENTIAL
ADJUSTMENT

SCREW

VALVE BODY

BYPASS
PISTON

DIFFERENTIAL SCREW'
SEALING CAP

(CAP MUST BE REPLACED

TO PREVENT REFRIGERANT LEAKAGE)

Fig. 13 — Capacity Control Valve

)^l2SECî2 —H

F—2-6 SEC

i BBi :

1 h—1 SEC m.5

1 €10

H-----1 h—5SEC i2

) EE

i

i

i

i

ri

1 1— ^-------------------- 40 SEC î 5

38AD024 THRU 044 UNITS

-5MIN----------------------

-4-45 SEC­

AMI

ÇÂÂ2~

)BB|

1BB2

i

38AB054 THRU 064 UNITS

NOTE- BLACK INDICATES CLOSED CONTACTS

38AB084 UNITS

Fig. 14 — Timing Charts

Control Circuit Reset

38AD024 THRU 044 AND 38AB084

-

Control

circuit locks out on these units in the event of oil

pressure loss, excessive motor temperatures, or

excessive

discharge

temperatures

Reset

is

accomplished by pushing reset button(s) in unit
control box.
38AB054 AND 064

Loss of oil pressure or

excessive motor temperatures cause control circuit
lock out on these units

Reset is accomplished by

pushing

reset

button

on

oil

failure

safety

switch(es). All other safety controls on each unit
are automatic reset, with restart accomplished
through unit timers.

Oil Pressure Safety Control (OPS)

for each com­

pressor will stop unit if oil pressure differential is
not established or maintaineci at either compressor.

If OPS stops unit, determine and correct the

cause (such as loss of compressor oil or flooded
compressor) before restarting unit. Failure to do so
will constitute abuse. Equipment failure due to

abuse is not covered by the Warranty

To restart

unit, push manual reset button in unit control box

(except 38AB054 and 064 units). Reset button is
on OPS on 38AB054 and 064.

Compressor Motor Protection

on 38AD024 thru

^ 044 and 38AB084 consists of three temperature

sensors (one for each phase) embedded in the

motor windings, and solid state modules in unit

control box.

Sensors are part of a temperature bridge. If a

motor winding overheats, the bridge circuit will
unbalance and a silicone-controlled rectifier in the
module will de-energize a relay which opens a set
of normally open contacts in the module and stops
the compressor.

If one

sensor fails, it can be jumped with a

75-ohm, 2-watt resistor. When checking or testing
module, do not apply more than 6 volts across
sensor terminals.

Many test instruments exceed this

voltage rating; check before using.

If a component in a module fails on 38AD024

thru 044, the entire module must be replaced. On
38AB084, the transformer is external to the
module and may be replaced separately. Replace
transformer with a Carrier specified balanced
transformer.

To restart compressor after shutdown due to

motor protection trip, push control circuit reset
button in unit control box.

Safety Relief

— All 38AB,AD units are protected

against excessive pressure by a fusible plug inserted
in the liquid line.

^ Winter Start Control

— On 38AB units (not

necessary on 38AD units because the timer
supplies this function), install a liquid line pressure-

stat (Carrier part no. HK02AB026) and evaporator
freeze-up protector (defrost thermostat, Carrier

part no. HH22UA025).

38AD control circuits incorporate a 150 sec­

onds timed bypass of the low-pressure switch to

in