allow unit to start under low-ambient conditions.

An evaporator freezestat must also be installed in

series with the control thermostat(s) to prevent

coil freeze-up (See lower part of Fig 15 — EDT

Wiring section.)

LIQUID LINE PRESSURESTAT - Connect to
system liquid line service valve port. Connect

switch into control circuit as shown on unit label
diagram or in Fig. 15. Pressurestat is set to cutout
at 5 psig with a differential of 10 psig. Do not

change setting

DEFROST THERMOSTAT - Position switch so
that moisture cannot enter switch insulator. Install
control with approximately 2 in. of top of thermo­
stat capillary passing thru lower part of evaporator

cod and with remainder of capillary inserted
between fins on entering air side of coil. Connect
thermostat electrical contacts into indoor cooling
thermostat circuit or in series with compressor
holding coil.

Thermostat is set to cut out at 25 F and cut in

at 55 F. Contact rating is 16 amps and 230 volts.
As evaporator coil frosts, cod fin temperature
drops to thermostat cutout setting, and stops
compressor. Evaporator fans keep running to
defrost cod with room air. As indoor coil defrosts,
fin temperature will rise to thermostat cut-in

setting. Compressor starts when cooling is required.

NOTE. Use a defrost thermostat on all systems

operating with outdoor temperatures below 45 F.

Fan Adjustment

— When replacing a fan, adjust fan

until top surface of hub plate is below the top of

the orifice ring as indicated in Fig. 16. Then,
tighten both setscrews, located over the keyway of
the fan hub of the motor shaft. Seal recessed area
of fan hub bore with Permagum to prevent rusting.

Lubrication

FAN MOTORS have permanently lubricated bear­
ings. No provisions for lubrication are made.

COMPRESSOR has its own od supply. Loss of oil

due to a leak in the system should be the only

reason for adding oil after the system has been in

operation.

To Add or Remove Compressor Od

1

.

2

.

3.
4.

Fig. 15 — Unit Wiring Changes for

Winter Start Control

Stop compressor and close suction service valve.
Pump down compressor to 2 psig. Stop com­
pressor and close discharge shutoff valve.

Relieve crankcase pressure by disconnecting

line, at compressor, which goes to low-pressure

connection of od safety switch.
Add oil thru oil filter connection.
Remove od thru drain plug in bottom cover.

Remove small amounts of od thru od discharge
connection with compressor running.

roft

3»^ A ...............................

i Fan

............L " '

38AD034

3SAD044

38

a

S«54

38A8iSii4

Fig. 16 — Fan Adjustment

11

Advertising