CONTROL POWER AT 38AD UNIT

tll5-l-60 VOLT t

TB
TC
TH

CR — Control Relay

HD — Heating Device
IFC — Indoor Fan Contactor

IFR — Indoor Fan Relay

LLS — Liquid Line Solenoid
R — Heating Relay (field-supplied 24-volt sealed coil, 10VA

maximum rating)

SDR — Solenoid Dropping Relay

— Terminal Board
— Thermostat, Cooling
— Thermostat, Heating

--------------Factory Wiring
------------- Field Wiring

^Jumper removed only when separate 24-volt power sources are

available for heating and cooling

fTo control heating device and provide automatic indoor fan

operation on heating

Fig. 12 — Control Circuit Wiring with 24-Volt

Accessories (38AD units only)

Preliminary Charge

— Refer to Carrier Standard

Service Techniques Manual, Chapter 1, Section 1-8,
for charging methods and procedures mentioned

below.
Charge system with approximately 25 lb of R-22

(75 lb for 38AD044, 38AB054,064 and 084 units)

by the Liquid Charging Method and Charging by
Weight Procedure.

Energize the Branch Circuit,

set space thermostat

above ambient.

Close field disconnect switch and

turn on unit circuit breakers. Be sure compressor
crankcase heater(s) is operating. Allow crankcase
heater(s) to operate a minimum of 24 hours before
starting unit.

To Start Unit,

set space thermostat below ambient,

to ensure circuit operation. On 38AD044 and

38AB084, push control circuit reset button(s).
After starting unit, there will be a delay of about

' 15 seconds (12 seconds on 38AD044 and

38AB084) before first compressor starts.

Charging System

1. Block condenser coils to maintain 125 F con­

densing temp at 280 psig, then add additional

charge to clear sight glass. (If long liquid lines

or vertical lifts greater than 25 ft are used, a
liquid line sight glass should be installed at
condensing

unit

and

used

for

charging

purposes.)

2. After sight glass has cleared, additional charge

must be added per Table 8, to flood subcooler
circuits in condensers.

After Charging the System,

allow unit to run for

about 20 minutes. Stop unit and check compressor
oil level. Add oil only if necessary to bring oil into

view in sight glass. If oil is added, run unit for

additional 10 minutes. Stop unit and check oil
level. If level is again low, add oil only after
determining that piping system is designed for
proper oil return and that the system is not leaking
oil. Check the operation of all safety controls.

Replace all service panels. Be sure that control

panel door is closed tightly.

Table 8 — Charging Data (R-22)

UNIT

REFRIG CHG (lb)

REFRIG

STORAGE

CAP. (Ib)t

Sub-cooler

Coil*

38AD024

8

70

38AD028

8

77

38AD034

7

99

38AD044

15

161

38AB054

12

154

38AB064

10

198

38AB084

21

322

*For maximum system capacity without receiver
fAt 120 F condensing temp with condenser 80% full of

liquid

NOTE

Values shown do not include charging requirements for
cooling coils and piping

SERVICE

Capacity Control

is by either one or two suction

pressure actuated unloaders. Each controls two
cylinders. Unloaders are factory set (see Table 9)
but may be field adjusted. No. 1 unloader is on
cylinder bank on same side of compressor as

terminal box.

CONTROL SET POINT (cylinder load point) is
adjustable from 0 to 85 psig. To adjust, turn

control set point adjustment nut (Fig. 13) clock­
wise to its bottom stop. In this position, set point

is 85 psig. Then, turn adjustment counterclockwise
to desired control set point. Every full turn
counterclockwise decreases set point by 7.5 psig.

PRESSURE DIFFERENTIAL (difference between
cylinder load and unload points) is adjustable from

6 to 22 psig. To adjust, turn pressure differential
adjustment screw (Fig. 13) counterclockwise to its

back stop position. In this position, differential is 6
psig. Then, turn adjustment clockwise to desired
pressure differential. Every full turn clockwise

increases differential by 1.5 psig.