Table 9 — Physical Data

UNIT

38AD024

38AD028

38AD034

38AD044

38AB054

38AB064

38AB084

OPER WT (lb)

1750

1900

2300 '

3200

3145

3830

4960

REFRIGERANT

R-22

Oper Chg (lb)*

28 0

30 5

35 5

66 0

57 0

71

0

132 0

COMPRESSOR

Reciprocating Hermetic — 1750 rpm

Number

1

1

1

2

2

2

2

Model

0ÓED250

06EE266

06EE275

06EA

250

06ED

250

06EA

250

06EE

275

06EA

275

06EE

275

06EA

299

06EE

299

Cylinders

4

4

6

4

4

4

6

6

6

6

6

Oil (pt)

14

14

19

14

14

14

19

19

19

19

19

Crankcase Htr

1 25 Watts

Pro tection

Solid State &. Ckt Bkr

Thermotector & Ckt Bkr

Solid State

& Ckt Bkr

Cap. Control

Suction Pressure Cylinder Unioader(s

No. 1

Unloader Settings (ps g)

Load

76

78

78

88

-

79

~

79

-

79

Unload

58

60

60

66

-

66

-

66

-

66

No. 2

Unioader Settings (psig)

Load

76

76

-

76

-

76

_

76

Unload

-

58

58

-

58

-

58

-

58

COND FANS

Axic 1 Flow;

Direct Drive

Number

3

3

3

3

6

S

6

Rpm

1140

1140

1140

1 140

1140

1140

1 140

Diam (in.)

26

30

30

30

30

30

30

Motor Hp (ea)

1

1

Cfm

18,200

25,200

28,200

31,000

50,400

56,400

62,000

COND COIL

Plafe Fins; 3-rowt

Sections

1

1

1

2

2

2

Face (sq ft)

35 4

39 0

49 6

60 4

78 0

99 2

120 8

Capacity (lb)t

70

77

99

161

154

198

322

ELEC CONTROLS

Time Guard Circuit**

Pre^surestat

Du al

, Cutout

High ^ ^ .

Cut-in

375 Psig

275 Psig

, Cutout

Low ^ ^ .

Cut-in

29 Psig

29 Psig

29 Psig

44 Psig

45 Psig

63 Psig

Pressurestat

Capacity Control

Cutout

57 Psig

57 Psig

Cut-in

-

-

87 Psig

87 Psig

Pressurestat

Oi 1 Pressure Contro

1

Cutout

5 Psi Above Suction Pressure

Thermostat

Fan Cycling

No. 1

Opens, 70 F; Closes, 75 F

No. 2

Opens, 57 F; Closes, 62 F

Thermostat

Opens

Discharge Line

290 F; Closes, 210 F

PRESS. RELIEF

Fusibl

e Plug

DISCHARGE LINE

1

1

2

2

2

2

CHECK VALVE

■*Approximate charge for maximum system capacity Holding charge

factory supplied with all units

fUnit 38AD044 and 38AB084 have 4 row coil

^Storage capacity at 120 F condensing temp with condenser 80%

full of liquid

**Short-cycle protection

Time Guard Circuits

BASIC FUNCTIONS OF TIME GUARD CIRCUIT
on all units provide for normal (12 to 15 sec)
momentary delays after the thermostat closes and
before compressor(s) start. The circuit also pro­

vides for a longer delay (4 min 45 sec to 5 min

30 sec) in the event of thermostat short cycling or

momentary power failure.

38AD024 THRU 044 UNITS

In addition to the basic functions, timers in

these units provide additional delays for oil
pressure switch bypass (40 sec), winter start
provision ( 1 5 0 sec) bypass of low-pressure switch
and part-winding start (1 sec), if used.