Typical piping and wiring, Application data, Cont) – Carrier ZONE-MIZER 50ME User Manual

Page 43

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

exercise care when selecting this equipment for use with a
multizone. The design and installation of vibration rails on a

Carrier 48MA/50ME should ensure that the interfacing of
the vibration isolator and the curb maintain watertight
integrity.

Thermostat usage and control

Usage — The thermostats used with the 48MA/50ME
units are either a 2-step heat/1-step cool or 2-step heat/
2-step cool. A single module can have only one step of
cooling and heating. When 2 or more modules are grouped
together, use the 2-step heat/2-step cool thermostat.

Application data

(cont)

Modules are grouped together by the installation of
factory-supplied jumpers on the unit zone control board.

The thermostats are automatic changeover with a 3 F

dead spot between heating and cooling. There is a 1 F
differential between the first and second steps of heating or

cooling. Two subbases are available for use with the thermo­
stats; one with off-heat-auto.-cool switch and one without
switches for tamperproof installation. The tamperproof
subbase has provisions for locking the thermostat covei
and temperature selectors. Refer to 48MA/50ME wiring
booklet for thermostat wiring connections.

Typical piping and wiring

ROOF
CURB

POWER

SUPPLY

WIRING

EIGHT-ZONE
UNIT SHOWN

ZONE THERMOSTAT

WIRING(24 V)

^CONDENSER AIRFLOW

[^RETURN AIR

I^COOL AIR TO ZONE

I^WARM AIR TO ZONE

GAS CONN

(48MA0NLY)

c>

OUTDOOR MAKEUP AIR

43