Performance data

TYPE

FILTER RESISTANCE (in. wg)

UNITS 50ME016,

024 AND 028

FILTER

CFM

CFM

6000

8000

10,000

10,000

12,000

Standard

.025

044

069

069

099

Hi Efficiency

.024

043

069

069

099

Roll Filter

120

220

020

110

015

UNITS 50ME030,

034 AND 040

14,000

150
150

280

ELECTRIC HEATER PERFORMANCE

UNIT

HEAT-TO-

TOTAL

STEPS OF HEAT

KW/STEP

SOME

COOL RATIO

HEATER KW

PER MODULE

PER MODULE

016

75:1

53

2

33

&

1:1

70

2

44

024

1 5 1

106

3

44

028

75 1

66

2

3 3

&

1:1

88

2

44

030

1 5 1

132

3

44

034

75 1

79

2

3 3

&

1:1

106

2

44

040

1 5 1

158

3

44

GAS HEATING CAPACITIES (1000 Btuh)

INPUT

BONNET CAPACITY

UNIT

Total

Each

Total

Each Zone Module

48MA

Zone

Module

Full

016

432

324

024

432

324

028

540

54

405

40 5

030

540

405

034

648

486

040

648

486

At =

NOTES:
1 Ratings are approved for altitudes to 2000 feet At altitudes over

2000 ft, ratings are 4% less for each 1000 ft above sea level

2 At altitudes up to 2000 ft, the following formula may be used to

calculate air temperature rise

bonnet capacity

1 09

X

airquantity

At altitudes above 2000 ft, the following formula may be used

bonnet capacity

(24 X specificweightofair x 60) (airquantity)

Maximum allowable gas pressure is 10 5 in wg
Minimum allowable gas pressure for full rated
input is 5 0 in wg
Unit design is AGA certified

27