Guide specifications

(cont)

Exhaust feature — Provision shall be made for positive
exhaust of room air when unit is operating on economizer
cycle.

Remote control panel — Furnish a remote control panel
which contains a ventilation position adjustment, SYSTEM
switch, DAY/NIGHT switch, HEAT-COOL-AUTO.-OFF
switch and a clogged filter indicator light. Panel must have
provision for 3 additional indicator lights

High-efficiency filters — Furnish and install filters with
36.5% efficiency (NBS Dust Spot Test).
Roll filter — Install a motorized roll filter with 65 ft x 2-in.
of media, a runout switch and automatic advancing switch.

Cooling only — Unit shall have no heaters but shall have
24-volt heating controls and 115-volt power terminals
suitable for operation of field-installed steam, hot water
or electric heat.