M 10, Hh0iat171) — set anticipator for room, Table 4 — electrical data (60 hz) – Carrier 38QB User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Table 4 — Electrical Data (60 Hz)

UNIT

38QB

V/PH

OPER

VOLTAGE*

COMPR

FAN

FLA

BRANCH CIRCUIT

Min Wire

Size (AWG)t

Max \

'Vire ; 1 Min Gnd

Wire Sizel

Max Fuse**

or HACR Type

Ckt Bkr Amps

MCA

Max

Min

LRA

RLA

015

208-230/1

254

197

34

7 7

1 25

14

40 1

14

15

109

018

208-230/1

254

197

48

124

1 25

14

27 1

u

25

168

024

208-230/1

254

197

66

15 5

24

12

32 ;l

12

35

21 8

030

208-230/1

254

197

82

165

24

12

32 1

12

35

23 0

036

208-230/1

254

197

88

20 6

24

10

39 1

10

45

28 2

042

230/1

254

207

98

199

24

10

44 1

10

45

27 3

048

230/1

254

207

105

22 4

24

8

62 1

10

50

30 4

060

230/1

254

207

130

27 8

24

8

51 I

60

37 2

036

208-230/3

254

197

87

11 7

24

14

32 1

14

25

170

042

208-230/3

254

197

80

13 3

24

14

29 1

14

30

190

048

208-230/3

254

197

80

16 3

24

12

24 1

12

35

22 8

060

208-230/3

254

197

98

20 9

24

10

M 10

45

28 5

036

460/3

506

414

30

5 1

1 2

14

159 1

14

15

76

042

460/3

506

414

35

72

1 2

14

120 1

14

15

102

048

460/3

506

414

40

80

1 2

14

109 1

14

15

11 2

060

460/3

506

414

49

104

1 2

14

_3I

■__________ ______

20

142

AWG — American Wire Gage

FLA — Full Load Amps
FIACR — Heating, Air Conditioning and Refrigeration

LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
RLA — Rated Load Amps

‘Permissible limits of the voltage range at which the unit will

operate satisfactorily

tCopper wire sizes based on 60C Use copper wire only.
tRequired when using nonmetallic conduit

“Time-delay fuse

NOTE: All units have 24-v control circuit which requires external
power source

CONNECT CONTROL POWER WIRING (24 V)
— Extend wiring thru hole provided (Fig. I) and
into low-voltage section of unit control ring.
Connect leads to control wiring terminal board as
shown in Fig. 5.

Use indoor unit transformer as 24-v supply for

system. At least a 60-va transformer is recom­
mended.

Carrier

approved

indoor

units

are

equipped with a 60-va transformer. See indoor

unit data.

Use Carrier accessory indoor thermostat with

suhbase, Table 3.

START-UP

The 38QB unit is equipped with a crankcase

heater. It is recommended that heater be energized a
minimum of 24 hours before starting unit. To ener­
gize heater only, turn the thermostat to OFF posi­
tion and close electrical disconnect to heat pump.

Heat Anticipator Settings for Room Thermo­

stat

(HH0IAT171) — Set anticipator for room

^ Table 5 — Thermostat Anticipator Settings

UNIT

38QB

FIRST-

STAGE

ANTICIPATOR

SETTING

INDOOR

UNIT WITH

ELECTRIC

HEATER

HTR

KW

SECOND-

STAGE

ANTICIPATOR

SETTINGS

015
018
024
030
036

042
048
060

Fixed

40DQ and

40AQ Fan Coil

with 40AQ Htrs

or 40QB,QH

Fan Coil with

40QB Htrs

50

7 5

100

25

150

20 0
25 0

50

30 0
34 0

75

thermostat according to Table 5. These settings may
be changed slightly to provide a greater degree of
comfort for a particular installation.

Accessory Outdoor Thermostat

provides adjust­

able outdoor control of accessory electric heater.
This thermostat makes contact when a drop in out­
door temperature occurs. It energizes a stage of elec­
tric heat when the outdoor temperature setting is
reached, provided the room thermostat is on the
second stage of heating. One outdoor thermostat is

recommended for each stage of electric heat after the

first stage. Set the outdoor thermostat(s) pro­
gressively lower for each stage. Refer to heat load of
building and unit capacity to determine the correct
outdoor thermostat settings.

The accessory supplemental heat relay is required

when 2 outdoor thermostats are used. It is auto­
matically energized by the manually operated
supplemental heat switch in the indoor thermo­
stat subbase. The thermostat locks out compressor
and the relay bypasses the outdoor thermostats for
electric heater operation during heat pump shut­
down. When one outdoor thermostat is used, a sup­
plemental heat relay is not required. The supple­
mental heat switch in the indoor thermostat subbase
bypasses outdoor thermostat, locks out compressor
and activates electric heater.

MOUNT OUTDOOR THERMOSTAT on control

ring, to the left of the low-voltage control connec­
tion. See Fig. 1.

Attach brackets with short sheet metal screws to

avoid contaet with coil. Leave capillary tube coiled
in control compartment making sure it is clear of all
electrical connections and sharp metal edges.