Fig. 14 — Charging Chart — Cooling,

50EQ028

3 3 41

Э

a

SUCTION

3

6C

-INE TEMP

7

ERATURE

0 e

(F)

0

-i 4 10 № 22 27

SUCTION LINE TEMPERATURE (C)

Fig. 15 — Charging Chart — Cooling,

50EQ034

Table 6 — Air Quantity Limits

UNIT

MINIMUM CFM

MAXIMUM CFM

50EQ

STANDARD AIR

STANDARD AIR

024

6,800

9,000

028

8,300

12,000

034

10,080

14,000

NOTES

1 Operation below minimum limits may cause a high

pressure condition when unit is on heating cycle

2 The operation of electric resistance heaters above 47 F

when compressor heat is operational is not recom­

mended below minimum cfm's Field-adjustable ther­
mostat in unit locks out electric heat

To check system operation during heating

cycle, use correct Heating Cyele Operation Check
Chart (Fig. 16, 17, or 18). This chart indicates
whether a correct relationship exists between sys­
tem operating pressures and indoor and outdoor

entering air temperatures. If pressure and tem­
perature lines do not intersect on chart, the system
refrigerant charge may not be correet or other sys­
tem abnormalities may exist. Do not use Heating

Cycle Chart to adjust refrigerant charge.

Fig

16 — Heating Cycle Operation Chart

50EQ024