Route thermostat cable or equivalent single leads

of no. 18 AWG colored wire from subbase terminals
thru connectors in unit base pan or side panel (Fig.

3) to low-voltage connections in control box as

shown in Fig. 9. Use no. 16 AWG wire for lengths
exceeding 50 feet. Set heat anticipator settings as
indicated in Table 1.

Refer to accessory remote control panel instruc­

tions as required.

Outdoor Air Thermostat

— Unit is equipped with

a field adjustable outdoor air thermostat. Thermo­
stat is shipped taped to right-hand side of unit
control box. Upon start-up, set the thermostat
“close setpoint” to the building load balance point
and unit capacity. Above the setpoint, the space
thermostat controls 2 stages of compression heat
and electric heat is locked out. Below the setpoint,

one stage of compression heat is available and elec­
tric heat is controlled by the second stage of the
space thermostat.

Compressor(s)

— Loosen compressor hold-down

bolts until sidewise movement of the washer under
each hold-down bolt head can be easily obtained.

Do not loosen completely as bolts are self-locking

and will maintain their adjustment.

Open the compressor discharge and suction

service valves. Replace and tighten valve caps to
prevent leaks.

Liquid Line Service Valves

— Open the liquid line

service valves. Replace caps and tighten to prevent
leaks.

START-UP

Cooling

1. Open compressor service valves. Replace valve

caps to prevent leaks. Make sure crankcase
heater has been on for at least 24 hours to
drive out any liquid refrigerant in compressor
crankcase. Check compressor oil level. Oil sight
glass should be about half full.

2. Be sure that liquid line service valve is open.

3. Check that setscrews are tight in fan bearing

locking collar, pulley and fan blades.

4. Check pulley alignment and belt adjustment.

Remove tape on indoor fan pulley.

5. Check that internal power wire terminal screw

connections are tight.

6. On 3-phase units, check for correct fan rotation.
7. Set system selector switch at COOL and fan

switch at AUTO. Adjust thermostat at a setting

below room temperature. Compressor no. 1 will
start on closure of no. 1 contactor. An addi­
tional rise in room temperature closes cooling
contactor no. 2 in thermostat, energizing no. 2
contactor, no. 2 compressor will start.

8. Check cooling effect at duct supply outlets.

9. Check unit charge. Refer to Refrigeration

Charge in Service section.

Fig. 4 — Economizer Outdoor Air Inlet

Hood Assembly

Fig. 5 — Enthalpy Control Assembly

Fig. 6 — Enthalpy Control Assembly

Installation Details