MTD 243-723A User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

WARNING )

Provide adequate ventilation for toxic

exhaust gases and cooling air flow.

Turn key to "OFF" position to stop enigne. See

"shut-down procedure'.

BREAK-IN PROCEDURE

Controlled break-in helps insure proper engine and

generator operation. Follow engine break-in procedure
outlined in engine manual.

A

CAUTION

Allow generator to run at no load for
5 minutes upon initial start-up to
permit

engine

and

generator

to

stabilize.

DETERMINING TOTAL WATTAGE

To prevent overloading the unit, it is necessary to add

up the total wattage of the connected load.

1.

Electric motors require more power when starting

than running. First, determine your largest motor
starting requirement. To this figure, add the total
wattages of all other items you want to connect
to the generator at the same time. If only volts
and amps are given, volts x amps = watts. 1,000
watts - 1 KW.

2.

This total should not be more than the rated

wattage

for

your

unit

as

shown

in

the

specifications.

3. Always start your largest electric motor before any

other load is applied.

A

CAUTION

Do not apply heavy electric load during

the first 2 or 3 hours of operation.

APPLYING LOAD

This unit has been pretested and adjusted to handle
its full rated capacity. When starting the generator,
disconnect all load. Apply load only after generator
is running.

A

CAUTION

Overloading the unit may burn out
the unit and/or anything connected to
it!

Keep load within nameplate rating. Continuous

overloading may cause damage to the generator and
shorten its life.

The following should be observed;

Single Voltage Units. These models are equipped with
one circuit and one duplex receptacle. The total
rated wattage can be drawn from this circuit.

Dual Voltage Units. See Figure 2 and Figure 3. These

models are equipped with two 120 volt circuits. (A
and B). These two 120 volt circuits are combined to
form the 240 volt circuit, (C).

You can use 75% of the nameplate rating from either

120 volt circuit (A or B) but not from both at the

same time.

When using both 120 volt and 240 volt equipment, the

120 volt load from circuit A or B plus one-half of the

240 volt load from circuit C must not exceed 75% of
the nameplate rating.

FIGURE 2

A В

FIGURE 3

4

Advertising
This manual is related to the following products: