In addition to the effective use of sound insulatingma-

terials, construction of a special noise abatement
compartment might be considered to reduce noise

levels. Such a compartment might be constructed as

follows (Figure 11):

Figure 11 — Typical Noise Abatement

Compartment

PLYWOOD
5/8” THICK

EXTERIOR

SOUND
INSULATION

METAL LINER

FIBERGLASS
INSULATION

PLYWOOD
5/8" THICK

DANGER; DO NOT INSTALL ANY INSULATION OR
OTHER ABSORBENT MATERIALS ON THE INTERI­

OR OR UNDERSIDE OF THE COMPARTMENT
FLOOR.

Seal all compartment door edges to prevent noise leak­
age around the door perimeter.

Line the compartment door interior (except for air open­
ings) with suitable, fire proof sound insulation (such as 1 -

inch thick fiberglass with a 2-pound density) See Figue

12

.

Figure 12 — Typical Compartment

Door Construction

Use 5/8-inch thick or 3/4-inch thick plywood in the com­

partment.

Construct the compartment floor of a double thickness of
5/8-inch or 3/4-inch plywood.

Line the compartment interior walls and floor, as well as

the underside of the floor, with 26-gauge galvanized

steel.

Vapor seal all compartment seams and joints.

Over the galvanized steel lining, install a selected combi­

nation of acoustical materials as mentioned in “Sound

Insulating Materials."

A TIMES B MUST EQUAL_AT LEAST

100 IN.'OF FREE AIR OPENING

9