Compensating for restriaions, Testing the installation, Compensating for restrictions – Generac Power Systems 91355 User Manual

Page 13

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Figure 16 — Air Inlet Using Ductwork

Figure 17 — Air Inlet in Vehicle Skirt

RECOMMENDED CLEARANCE • 1-1/2 IN. (38.1 MM)

^

MINIMUM CLEARANCE - 1 IN. (25.4MM)

.-L

VEHICLE FLOOR

ENGINE
SIDE
VIEW

VEHICLE

.SKIRT

J

COMPENSATING FOR

RESTRiaiONS

Such materials as screening, louvers, or expanded
metal can restrict the free flow of air. Compensate for

this restriction by making the actual air opening pro­

portionately larger.

Some materials may offer only a 60 percent “free air
inlet area.” Other more efficient materials may provide
up to a 90 percent free air inlet area. The percentage
of free air inlet opening is usually available from the
material supplier or manufacturer.

TO DETERMINE THE ACTUAL AIR INLET OPEN­

ING SIZE REQUIRED, DIVIDE 100 SQUARE INCH­
ES BY THE PERCENTAGE OF FREE AIR INLET
AREA FOR THE MATERIAL YOU WILL USE.

For example: If you plan to use screening with an

80% free air inlet area, divide 100 by 0.8, which

results in 125 square inches. Minimum actual size of

air inlet opening in this casé is 125 square inches. An
opening that measures 8 inches wide by 16 inches
long provides the required air flow (8 x 16 = 128
square inches).

TESTING THE INSTALLATION

Generac recommends testing the installation to be
sure adequate cooling air flow is available to the unit
before placing the unit into service. If the unit shows
signs of overheating, you will need to enlarge the air
openings. Never place a unit into service until
absolutely certain that cooling and ventilation is ade­
quate.

IMPORTANT: YOU MUST TEST THE INSTALLA­

TION ESPECIALLY IF YOU BRING IN AIR FROM

BELOW THE GENERATOR SET.

11

Advertising