RECONNEaiON FOR DUAL VOLTAGE

You can reconnect the generators to supply a dual
voltage AC output, if desired. That is, units may be

reconnected to operate 120 and/or 240 volts, 1-
phase, 60 Hertz, AC loads. This is done by connect­
ing the hwo stator AC power windings in series as it is
shown in Figure 2.

IMPORTANT:

UNITS RECONNECTED FOR

120/240 VOLTS DUAL VOLTAGE OUTPUT WILL
NOT BE LISTED PER RVIA.

NOTE:

The Q-40G can NOT be reconnected for a

dual voltage output of 120/240 volts AC.

Figure 2 — Reconnection for Dual Voltage Output

When reconnecting for dual voltage output, the

installer should replace the main circiut breakers
(CB1 and CB2) with a single adequately rated circuit
breaker. Rated maximum continuous load currents
are listed below:

• NP-50LP —18.8 AC amperes

• NP-50G — 20.8 AC amperes

• Q-55G/LP — 22.9 AC amperes

• NP-66G/LP — 27.5 AC amperes

• Q-70G/LP — 29.1 AC amperes

NOTE:

This option is unavailabe on the Q40 model.