Carrier Infinity SYSTXCCUID01 User Manual

Page 11

Advertising
background image

Service = HEAT PUMP / AC STATUS

STAGE: (HEAT / COOL):

OFF, LOW, HIGH

Displays stage of heating or cooling that the heat pump/AC is
delivering.
DEFROST:

NO, YES

Displays status of defrost mode if heat pump.

AIRFLOW CFM:

Indoor unit cfm measurement.

BLOWER RPM:

RPM feedback from indoor motor.

COIL TEMP:

Degrees F.

Temperature of the outdoor unit coil (only available on 2-speed
communicating outdoor units).

STATIC PRESS:

Static pressure of indoor unit.

Service = LAST 10 SYSTEM FAULTS

This screen will show last 10 faults that occurred throughout the
system. Each fault has the time and date of incident recorded.
Service technician should enter current date in

″TODAY’S

DATE

″ menu section before checking and logging the last 10

system faults. Each fault has a two-letter acronym preceding the
fault name to identify which piece of equipment generated the
fault.

HP = heat pump

AC = air conditioner

FN = furnace

FC = fan coil.

Service = RUN / FAULT HISTORY

The indoor unit and outdoor unit (if communicating) has the
following histories:

NOTE:

For Critical Fault Screens, see Trouble Shooting section

in this document.

Resettable Faults:

Fault counters for each piece of equipment that can be reset.

Cycle Counters:

Number of heat/cool/power cycles the unit has performed.

Run Times:

Lifetime hours of operation in heating, cooling, and how long
the unit has been powered.

Service = TODAY’S DATE

This menu item allows the installer to enter the current date. It
is used for time/date stamping of system faults. This should be
entered every time prior to viewing

″LAST 10 SYSTEM

FAULTS

″ section.

Service = MODEL / SERIAL NUMBERS

If available, this menu item allows the installer to view the
model number and serial number of all communicating pieces
of equipment in the system.

Service = SERVICE PHONE NUMBER

This menu item allows the installer to enter a name and phone
number that the homeowner can call for future service of the
system. This name and phone number will appear to the home-
owner whenever a service reminder pop-up message is displayed
(i.e. Change Filter, etc.)

To edit:

Use Temp +/- button to move cursor left and right.

Use Time +/- button to select numbers and letters.

Use Scroll button to move up and down between NAME and
NUMBER.

OPERATIONAL INFORMATION

Continuous Fan Operation

Pressing FAN button will scroll through the following:

AUTO = No fan operation except during equipment operation.

LOW = Approximately 50% of High Speed operation.

MED = The difference between High and Low speed operation.

HIGH = Highest of either High Heating or High Cooling CFM.

Five-Minute Compressor Timeguard

This timer prevents compressor from starting unless it has been off
for at least 5 minutes. It can be defeated by simultaneously
pressing the Fan and Temp + buttons.

Emergency Heat (for heat pump applications)

To activate Emergency Heat, you must press and hold the HEAT
button for 3 seconds to activate.

Keypad Lockout

Keypad can be locked by pressing Fan and Humidity/OAT buttons
at the same time for 3 seconds. When keys are locked, a lock
symbol will appear in the upper left corner of screen. Follow same
procedure to unlock keypad.

Heat and Cool LED

The Heat and Cool LEDs will pulsate during actual equipment
operation.

Equipment Cycle Timer (adjustable 4-6 cycles per hour)

This timer prevents the start of a heating or cooling cycle until 15
(or 10) minutes after the last start of the same cycle. Its function is
to assure that the equipment is not cycled more than the selected
times per hour. This timer is adjustable from 4 to 6 cycles per hour.
This timer is defeated for one cycle when the desired temperature
is manually changed. It can also be defeated for one cycle by
simultaneously pressing the Fan and Temp + buttons.

Ten-Minute Staging Timer

In multistage heating or cooling, this timer prevents any higher
stage from turning on until the preceding stage has been on for 10
minutes. This timer is defeated if temperature error is greater than
5°F (usually due to a large change in desired temperature).

Three-Minute Minimum On Time

In normal operation, when a stage turns on, it will remain on for a
minimum of three minutes. If the set point is changed, this timer is
automatically cancelled, allowing the equipment to turn off imme-
diately when the demand is removed.

Heat/Cool Set points (Desired Temperatures)

A minimum difference of 2° (default) is enforced between heating
and cooling desired temperatures. This is done by allowing one
setting to

″push″ the other to maintain this difference. This

difference is adjustable via the Install/Service menu under Ther-
mostat Setup.

Auto Changeover

When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the set point is changed, the
30-minute requirement is defeated. This Auto Changeover time is
adjustable via the Install/Service menu under Thermostat Setup.
Range = 5 - 120 min.

Smart Recovery

11