B. ground-level installation, C. clearances – Bryant 542E User Manual

Page 2

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

542E REQUIRED CLEARANCE (Inches)

Top of unit ............................... 48 Blower access door end..
Duct side of unit...................... 12 End opposite blower
Compressor access door access end

side........ ............................. 30 Bottom of unit above

..30

.112

■ anticipated snow level.. ■6

i-E

. CONTROL ACCESS DOOR^ 7

\ /-4

oia

r-i DIÁ

HIGH-VOLTAGE

.«------------------

A

COMPRESSOR
ACCESS DOOR

INLET WITH MULTIPLE.
KNOCKOUTS

U-N"

“T

M

_L

-SUPPLY-AIR

,MPT

DRAIN

^CONNECTION

ELECTRIC HEAT

HIGH-VOLTAGE INLET WITH
MULTIPLE KNOCKOUTS

A79071

542E DIMENSIONS (Inches)

Size

A

B

c

D

E

F

G

H

J

024 & 030

60-3/16

32-3/16

24-13/16

21

11-1/2

13-5/16

54

6-7/8

6-15/16

036

60-3/16

32-3/16

24-13/16

21

13-3/4

13-5/16

54

4-5/8

6-15/16

042, 048, & 060

68-3/16

40-3/16

30-13/16

21

16-3/8

17-5/16

61-3/16

5-1/8

' 7-1/2

Sizes

K

L

M

N

P

R

S

T

U

V

024 & 030

18-1/8

3

15-3/32

12-9/16

13

,28-9/16

37-1/8

2

7/8

27-3/8

036

18-1/8

3

15-3/32

12-9/16

13

28-9/16

37-1/8

2

7/8

27-3/8

042, 048, & 060

25

3-3/8

20-3/32

15-1/8

16-19/32

34-9/16

44-1/4

2

7/8

33-11/16

Figure 3--542E Dimensional Drawing

TABLE l-RATINGS, PERFORMANCE, & RECOMMENDED FILTER SIZES

MODEL

542E

542D

SIZE

024

030

036

042

048

060

060

SERIES

A

A

A

A

A

A

A

Rated Heating Capacity® 47°F (Btuh)*

26,000

30,000

35,000

43,000

48,000

58,000

58,000

Total Power Consumption (Watts)*

2850

3300

3850

4700

5100

6300

6300

COP*

2.7

2.7

2.7

2.7

2.8

2.7

2.7

Rated Heating Capacity® 17°F (Btuh)*

14,000

16,000

18,000

22,000

25,000

31,500

31,500

Total Power Consumption (Watts)*

2300

2650

3000

3650

4150

5200

5200

COP*

1.8

1.8

1.8

1.8

1,8

1.8

1.8

Rated Cooling Capacity @ 95°F (Btuh)*

25,500

30,000

35,000

43,000

47,000

58,000

58,000

Total Power Consumption (Watts)*

3350

3800

4650

5300

6100

7700

7700

EER

7.6

7.9

7.5

8.1

7.7

7.5

7.5

Rated Indoor Airflow (Ft3/Min)*

850

1050

1300

1550

1700

2000

2000

Rated External Static Pressure (In. wc)*

0.3

0.3

0.3

0.3

0.3

0.3

0.3

ARI Sound Rating Humbert

19

19

19

18

18

20

20

Recommended Minimum Filter Size (Sq ln.)t

Standard-Type

408

504

624

744

816

960

**

Cleanable- or High-Capacity-Type

265

328

406

484

530

624

**

* Rated in accordance with ARI Standard 240-77.

t

Rated in accordance with ARI Standard 270-75.

i Recommended field-supplied filter sizes shown are

**Two 20

X

20

X

2 high-capacity filters are furnished

based on a velocity of 300 ft/min at the rated indoor airfow.

with Model 542D060.

plenum, the accessory roof mounting curb must be installed
on and flashed into the roof before unit installation. The in­
structions for installing the curb are packaged with the
curb.

CAUTION:

Be sure that the roof will support the additional

weight. Refer to Figure 5 or 6 for weight information. On a
downflow installation with a-Model 542D or a Model 542E
with an accessory downflow plenum where the accessory roof
mounting curb is not being used, the field-fabricated support

must be level and must properly support the unit and down-
flow plenum.

When installing a Model 542E without an accessory down­
flow plenum, place the unit on a level base that provides

proper support. On flat roofs, be sure that the unit is at least

4 inches above the highest expected water level on the roof
to prevent flooding. Consult local codes for installation re­
quirements.

NOTE:

See Figure 10 for a typical rooftop installation.

B. Ground-Level Installation

The unit must be placed on a solid level concrete pad that is
a minimum of 4 inches thick and that extends approximate­
ly 2 inches beyond the casing on all four sides of the unit.
The unit does not need to be secured to the pad except when

required by local codes.

NOTE:

See Figure 11 for a typical ground level installation.

C. Clearances

The required minimum operating and service clearances are

-

2

-

Advertising