Ii. condensate and defrost disposal – Bryant 542E User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

542D060 REQUIRED CLEARANCES (Inches)

Top of unit....... .........................48

Blower access door end__ 30

Compressor access door

End opposite blower

side................................. .......30

accessend..... 12

Side opposite compressor

Bottom of unit above

access door.......................... 12

anticipated snow level___ 6

-FRESH AIR

INLET HOOD

HIGH-VOLTAGE INLET

l-MPT

DRAIN

^CONNECTION

A79072

Figure 4—542D060 Dimensional Drawing

542E

Size

Shipping

Wt (lbs)

Operating

Wt (lbs)

Corner Wt (lbs)

A

B

C

D

024

320

310

78

75

77

80

030

334

324

81

78

81

84

036

348

338

85

82

84

87

042

453

443

111

107

110

115

048

465

455

114

110

113

118

060

490

480

120

116

120

124

Top View

Model 5420

A79116-A,

Figure 5—542E Corner Weights

shown in Figure 3 for Model 542E and Figure 4 for Model
542D.

CAUTION:

Any air restriction at the outdoor air inlet tthe

entire surface of the outdoor coil) can be detrimental to com­
pressor life.

The fan discharge is through the top of the unit. Do not
locate the unit under a complete overhead obstruction. Mini­
mum clearance under a partial overhang (such as a normal
house roof overhang) is 48 inches.

Be sure that the unit is located so that water, ice, or snow
from an overhang or roof will not fall directly on the top of
the unit and damage it. Be sure that grass, shrubs, or other
plants do not interfere with the airflow into or out of the
unit.

II. CONDENSATE AND DEFROST DISPOSAL
NOTE:

Condensate and defrost water disposal methods must

comply with local codes, restrictions, and practices.

Models 542D and 542E are designed to dispose of cooling
cycle condensate water through a 3/4-inch MPT plastic

UNIT-MODEL 542D060

Shipping Wt (lbs)

703

Operating Wt (lbs)

556

Unit Corner Wts (lbs)

A

B

C

D

144

138

134

140

ROOF MOUNTING CURB P/N 304851-302

Shipping Wt (lbs)

120

Operating Wt (lbs)

113

Curb Corner Wt (lbs)

A

B

C

D

27.5

27.5

29

29

UNIT&CURB

Combined Operating Wt (lbs)

669

Curb Corner Wts with
Unit on Curb

A

B

C

D

154

164

181

170

Figure 6—542D060 Corner Weights

drain fitting. To prevent damage during the shipping and
moving of the unit, this fitting is shipped inside the unit
compressor compartment (secured with tape). Locate this
fitting and insert the nonthreaded end into the drain hose
located in the compressor compartment. See Figure 12.

It is recommended that a 3-inch trap be installed in the
drain line to avoid improper drainage and to prevent leakage

of indoor air to the outdoors. See Figure 9. Make sure that
the outlet of the trap is at least 2 inches lower than the unit
drain pan connection to prevent the pan from overflowing.

-