TABLE IV-HEATING PERFORMANCE PRESSURES

Air Temp at

Indoor

Coil

Inlet l°F DB|

Pressure

Designation

(Psig)

5426024

542E030

542E036

Air Temperature at Outdoor Coil

F°0B

Air Temperature at Outdoor Coil

°F0B

Air Temperature at Outdoor Coil

°FDB

60

50

40

30

20

10

0

- t o

60

50

40

30

20

10

0

-10

60

50

40

30

20

10

0

-10

65

High Side 250 229 209 190 172 155 140 127 238 218 201 184 169 155 144 134 232 214 198 183 170 158 149 142

Low Side

69

59

49

41

33

25

18

14

71

60

50

41

32

24

18

13

64

52

46

38

31

25

18

13

70

High Side 268 243 220 199 180 162 147 134 251 231 211 195 179 165 153 142 247 230 213 198 184 171 161 152

Low Side

70

60

50

42

34

26

19

15

72

61

51

42

33

25

19

14

65

53

47

39

31

25

19

13

75

High Side 280 256 233 211 190 172 155 140 266 246 226 207 190 176 162 151 261 243 225 209 195 182 171 162

Low Side

71

61

51

43

35

27

20

16

73

62

52

43

34

26

20

15

66

54

48

40

32

26

19

14

Air Temp at

Indoor

Coil

Inlet (°F OBI

Pressure

Designation

(PsigI

542E042

542E04B

5420060 S 542E060

Air Temperature at Outdoor Coil

°FDB

Air Temperature at Outdoor Coil

°FDB

Air Temperature at Outdoor Coil

°FDB)

60

50

40

30

20

10

0

-10

60

50

40

30

20

10

0

-10

60

50

40

30

20

10

0

-10

65

High Side 254 234 216 193 171 159 148 136 262 237 214 193 174 158 144 134 268 238 210 186 166 151 142 136

Low Side

71

62

50

42

32

24

18

14

64

56

48

40

33

26

19

13

66

56

47

39

32

24

19

13

70

High Side 268 250 230 205 183 169 156 144 278 251 226 204 184 166 154 146 284 252 224 198 178 164 154 146

Low Side

72

63

51

43

33

25

18

14

65

57

49

41

34

27

20

13

67

57

48

40

32

25

19

13

75

High Side 283 266 243 218 194 180 166 153 290 266 242 220 201 184 169 158 298 268 238 212 190 174 162 156

Low Side

73

64

52

44

34

26

19

14

66

58

50

42

35

28

21

14

68

58

49

41

33

25

20

14

TABLE V-COOLING PERFORMANCE PRESSURES

Air

Tem p

at

Indoor

Coil

Inlet (°FW BI

Pressure

Designation

IPsigi

542E024

542E030

54ZE036

Air T em p a t O utdoor C oil i°F D BI

Air T em p a t O utdoor C oil i°FDBI

Air T em p a t O utdoor C oil l°FDBI

65

70

75

BO

B5

90

95

100

105

110

65

70

75

60

85

90

95

100

105

110

65

70

75

80

85

90

95

100

105

110

55

High S ide

157

174

190

207

224

240

258

276

293

313

150

166

181

196

212

226

246

264

282

302

182

196

211

227

242

259

276

294

312

332

Low Side

58

59

60

61

62

63

64

66

67

68

60

62

63

65

67

69

71

73

75

77

67

69

70

72

74

75

76

78

79

81

50

High S ide

162

179

195

212

228

244

261

279

296

315

153

169

185

200

216

230

250

268

286

306

185

199

215

231

246

263

280

298

316

336

Low Side

64

65

66

67

68

69

70

71

73

74

63

65

66

68

70

72

75

77

79

81

69

' 71

72

74

76

77

79

80

82

83

65

High S ide

168

185

200

216

232

247

264

282

298

317

157

173

188

204

220

235

255

273

291

311

188

203

219

235

251

268

285

303

321

341

Low Side

70

71

72

73

75

76

77

78

79

80

67

69

70

72

74

76

79

81

83

85

71

73

74

76

78

80

81

83

85

86

70

High S ide

173

191

206

223

239

253

270

288

304

324

160

177

192

208

224

240

259

277

295

315

192

207

223

239

255

273

290

308

326

346

Low Side

77

78

79

80

81

82

83

84

86

87

70

72

74

76

78

80

83

85

87

89

74

76

77

79

81

83

84

86

88

89

75

High S ide

175

192

209

227

242

260

278

294

315

336

164

180

196

212

228

244

264

282

300

320

196

212

228

244

260

278

296

314

332

352

Low Side

84

85

86

87

88

90

91

93

94

95

74

76

78

80

82

84

87

89

91

93

79

81

83

84

86

88

89

91

93

95

Air

Tem p

at

indoor

Coil

Inlet l°FW BI

Pressure

Designation

IPsigi

542E042

542E048

5420060 8 5 42E060

Air T em p a t O utdoor C oil (°F O B)

Air T em p a t O utdoor C oil l°F D BI

Air T em p a t O utdoor C oil l°FDB|

65

70

75

80

85

90

95

100

105

110

65

70

75

80

85

90

95

100

105

110

65

70

75

60

B5

90

95

100

105

110

55

High S ide

165

179

192

206

222

237

254

270

289

308

178

192

207

224

238

255

272

291

308

330

176

189

202

217

233

249

266

283

300

320

Low Side

60

62

63

65

67

68

70

72

74

75

61

62

63

65

66

68

70

72

74

76

59

61

62

63

65

67

68

70

72

74

60

High S ide

169

183

196

210 226

241

258

275

293

312

183

197

212

229

243

260

277

296

314

335

180

193

207

222

237

254

270

287

305

324

Low Side

64

66

67

69 70

72

74

75

77

79

65

66

67

69

70

72

74

76

78

80

63

65

66

67

68

70

71

73

75

77

65

High S ide

173

187

201

215

231

246

263

280

298

317

188

203

218

235

249

266

283

302

320

340

185

198

212

227

242

259

275

292

310

329

Low Side

68

69

71

73

74

76

78

79

81

83

69

70

71

73

74

76

78

80

82

84

67

69

70

71

72

74

75

76

78

80

70

High S ide

177

191

205

220

235

251

268

285

303

322

193

208

223

240

254

271

288

307

326

345

191

205

219

234

250

266

283

301

319

338

Low Side

72

73

75

77

78

80

82

83

85

87

73

74

'75

77

78

80

82

84

86

88

71

73

74

75

77

79

80

81

83

85

75

High S ide

181

196

210

225

240

256

273

290

308

327

198

214

229

246

260

277

294

312

332

350

198

212

227

242

258

274

292

310

328

346

Low Side

76

77

79

81

82

84

86

87

89

91

77

78

80

81

83

84

86

88

90

92

76

77

79

80

82

84

85

87

89

91

5. Evaluate system performance and refrigerant charge

level by comparing recorded readings with unit operat­
ing pressure/temperature tag.

6. When necessary, make slight adjustment to refrigerant

charge. If a substantial adjustment is indicated, deter­
mine abnormal condition in system that is causing inac­
curate readings, such as insufficient airflow across
either or both coils.

CAUTION:

If it i.-^ dcri-rrniin-d thaï ihe problem i' ai; o\cr

charged or undercharged unit’when operating in the heat­
ing mode, the refrigerant system should be evacuated and
recharged by adding the exact amount of R-22 refrigerant as
shown on the unit rating plate. A volumetric charging
cvliiuler or ac'. uraie .•fcoie should be u.~ed. \V her. operating in
the cooling mode, the operatiiig pre.ssiin' tempierature tag

may be used to adjust the charge.

C. Indoor Airflow & Airflow Adjustments

Model 542D and 542E units are equipped with direct-drive

blower motors. All motors have a high- and low-speed con­
nection except for 460-V motors which have only a high­
speed connection.
The system airflow for all units (except 460-V) can be
changed, when necessary, by changing the blower motor
speed connection from the factory setting to the unused
speed connection. The factory setting is indicated on the
unit wiring label.

CAUTION:

The recommended airflow is 400 to 450 ftVmin

per each 12,000 Btuh of unit capacity. Inadequate airJlmv
can cause unsatisfactory operation and performance. Cer­
tain unit./heater combinations can only be used with high
speed blower operation. See electric heater information

Table VI shows the air delivery performance of all units at
various external static pressures. Determine the airflow for
the system being installed as follows:

1. Start unit and measure static pressure in duct system at

unit.

-