DRIVE TYPES

L —Multi-speed direct drive heating—minimum cooling.

E—Multi-speed direct drive heating —maximum cooling

with evaporator motor relay.

COMPONENT INFORMATION

Motor - Type L - 4 Speed

1/8 HP (Sh. Pole)

Power Supply

120-60-1

Full Load Amps

6.3

Speed & Rotation

1050 CCW*

Motor - Type E - 4 Speed

1/3 HP (PSC)

Power Supply

120-60-1

Full Load Amps

6.5

Speed & Rotation

1075 CCW*

Blower Wheel Dia. & Width

10

X

8

Bore - Direct Drive

1/2"

Filter - Fiber Glass**

Inlet at Bottom

16

X

25

X

1"

External Filter Rack

P/N 60559D0I

16

X

25

X

1"

Internal Side Filter Rack

16

X

25

X

1"

Rear Drop Duct P/N 60569D02

16

X

25

X

1"

Bottom Enclosure

P/N 56201C07

* Rotation viewed from end opposite shaft

**Use multi-velocity filters above 1000 CFM

CONNECTIONS

Gas Supply NPT - Natural

1/2

- Propane

1/2

Electric Supply - Direct Drive

120-60-1

Branch Circuit Wire Size

AWG

14

Fuse Size

Amps

15

Control Circuit Power Available*

Type L

VA

10.8

Type E

VA

7.2

Flue Size

Inches

5 (Oval)

Duct - Inlet at Bottom

D&W

22-1/4

X

14-1/4

Inlet Ext. Filter Rack

H&W

14

X

23

Inlet Drop Duct

D&W

12

X

16-5/8

Discharge

H&W

20

X

16-5/8

AIRFLOW FOR INDICATED AIR TEMPERATURE RISE^

TEMP RISE °F

70

75

80

85

90

95

100

AIRFLOW CFM

993

926

869

818

772

732

695

*At Rated Input