Accoutrements HIGH ECONOMY GAS FURNACE 1200-103B User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

COMBUSTION AND VENTILATION AIR

The

furnace

and

furnace

room

must

have

an

adequate

supply

of

air

for

safe

combustion

and

ventilation.

The

provisions

necessary

to

assure

an

adequate

air

supply

will

vary

depending

upon

differences

in

the

tightness

of

house

construction

and

in

the

location

of

the

furnace.

Methods

of

providing

air

from

some

typical

situations

are

described

below.

Consult

local

codes

and

ordinances

for

requirements

applicable

to

your

specific

furnace

installation

conditions

and

comply

with

them.

In

the

absence

of

local

codes

and

ordinances,

comply

with the National Fuat Gas Code, ANSI Z223.1-19B0.

EXAMPLE I - FURNACE LOCATED IN AN UNCONFINED SPACE

A.

If

the

furnace

is

located

in

a

basement

or

other

large,

open

area

of

a

conventionally

built

house

(loose

construction),

the

air

that

leaks

into

the

building

normally

will provide an adequate air supply.

B.

If

the

furnace

is

located

in

a

tightly

constructed

building

(storm

windows,

weather

stripping,

cracks

caulked,

etc.)

an

outdoor

air

intake

must

be

provided.

Example

2,

Section B, shows a typical method.

EXAMPLE 2 - FURNACE LOCATED IN A CONFINED SPACE

A. When the furnace is in a closet or utility room, install two

open grilles In a wall or door opening to the rest of the
house. One square inch for each 1000 Btu/h of total input

rating of all gas appliances in the confined space. Refer to
Figure

~T,

The

grilles

must

communicate

with

other

open

areas having adequate air infiltration from outdoors.

If

the

building

is

tightly

constructed,

not

enough

outside

air

may

enter

for

safe

combustion.

Install

a

fresh

air

duct

from

a

point

near

the

burners

to

the

outside

or

to

a

ventilated

attic

or

crawl

space.

Refer

to

Figure

3.

This

duct must have a free area of at least one square inch for
each 4,000 Btu/h of total Input of aii gas appliances in the

space.

The

minimum

dimension

of

a

rectangular

duct

must

not be lass than three inches.

CAUTION:

WHEN

A

FURNACE

IS

INSTALLED

IN

A

CLOSET

OR UTILITY ROOM, NEVER USE THIS ROOM AS A

RETURN AIR PLENUM.

FIGURE 2 — FURNACE LOCATED IN CONFINED SPACE

FIGURE 3 — FRESH AIR DUCT FOR TIGHTLY SEALED

BUILDING

This

furnace

must

be

vented

directly

to

the

outside

through

a

suitable

chimney.

This

furnace

as

shipped

from

the

factory

is

suitable

for

a

^dicated

flue

only.

It

should

not be

vented

and

terminated

horizontally

through

a

side

wall

and

Is

not

suitable

for

use

with

plastic

pip*-

tffth"^'the

"

addition

of

optional

field-in

stalled

Common

voting

Kit

8620-005

or

-006,

it

is

suitable

to

common

vent

thia

furnace

along

with

another

gas

burning

appliance

to

a

single

chimney

for

eese

of

installation.

Refer

to

section

on

Comann

Venting

beginning

on

page

11

of

this

instruction

manual

for

complete

details.

The

vent

must

be

installed

in

compliance

with

the

National

Fuel

Gas

Coda

(ANSI

Standard Z223. 1-1980, ] and these instructions.

GENERAL INSTRUCTIONS

1.

The

vent

connector

must

be

aluminum

pipe

and

shall

be

the same siia as the flue outlet on the furnace. Keep the
vent

as

short

and

direct

as

possible.

Type

B-1

pipe

is

recommended.

2.

Maintain

a

minimum

clearance

of

6"

(1" for

B-1)

to

any

portion

of

the

vent

connector

from

any

adjacent

combustible

materials.

Single

wall

vent

connector

is

permitted only within the same space (room or area] at the
furnace.

B-1

vent

is

required

whenever

the

vent

is

enclosed

or

passes

through

floors,

walls,

ceilings,

roofs

or

furred-out

spaces.

Joists,

studs,

floors,

dry

wall,

paneling,

sheeting,

rafters,

roofing

and

other

matcriais

classified

as

combustibia

must

not

be

closer

than

1“

clearance to the B-1 vent.

3.

If connected into masonry chimney, the vent pipe must be

inserted

into,

but

not

beyond

the

inside

wall

of

the

chimney.

4.

The gas vent must extend at least 2 feet above the highest

point

where

it

passes

through

the

roof

of

a

building

(3

feet

for

a

chimnay]

and

at

least

1

foot

hlghar

than

any

portion

of

a

building

within

a

horizontal

distance

of

10

feet. See Figure 4.

5.

The

vent

pipe

system

shall

be

installed

so

as

to

avoid

excessive

turns

which

create

unnecessary

resistance

to

flow of vent gases.

Advertising