Accoutrements HIGH ECONOMY GAS FURNACE 1200-103B User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

fi.

7.

8

.

9.

10

.

Horizontal

runs

shall

be

as

short

and

direct

as

possible.

The

maximum

length

of

a

single-wall

vent

pipe

shall

not

exceed

75

percent

of

the

height

of

the

vent

system.

The

maximum

length

of

a

Type

B-1

double

wall

flue

connection

shall

not

exceed

100

percent

of

the

height

of

the

vent

system.

All

horizontal

vent

pipe

shall

be

pitched

upward

from

the

furnace at least 1/4 inch per foot.

All

vent

systems

shall

be

adequately

supported

to

maintain

proper

clearances,

to

prevent

physical

damage,

and

to

prevent separation to joints.

Vents

passing

through

an

exterior

combustible

wall

must

use a ventilated wall thimble. See Figure 5.

FIGURE 8 — GAS PIPE SIZES — NATURAL GAS

Vents

passing

through

floors

or

ceilings

must

fire-stopped. See Figure 6 and Figure 7.

be

Length

of

Pipe, Ft.

Pipe Capacity — Btuh Per Hour

Input Pipe Size

1/2"

3/4“

1"

1-1/4"

10

132,000

278,000

520, 000

1,050,000

20

92,000

190,000

350,000

730,000

30

73,000

152,000

285,000

590,000

40

63,000

130,000

245,000

500,000

50

56,000

115,000

215,000

440,000

60

50,000

105,000

195,000

400,000

70

46,000

96,000

180,000

370,000

80

43,000

90,000

170,000

350,000

too

38,000

79,000

150,000

305,000

GAS SUPPLY AND PIPING

general

recommendations

1.

Be

sure

the

gas

line

complies

with

the

local

codes

and

ordinances,

or

in

their

absence

with

National

Fuel

Gas

Code, ANSI Z223.1-1980.

2.

A sediment trap

or drip leg must be installed in

the

supply line to the furnace.

3.

A ground joint union shall be installed

in the gas

line

adjacent to and

upstream from the gas valve

and

downstream from the manual main shut off valve.

4.

A

1/8”

N.P.T.

plugged

tapping

accessible

for

test

gauge

connection

shall

be

Installed

immediately

upstream

of

the

gas

supply

connection

to

the

furnace

for

the

purpose

of

determining the supply gas pressure.

5.

A

manual

shut-off

valve

shall

be

installed

in

the

supply

gas line external to the furnace (see Figure 9 and 10).

6.

Use steel or wrought iron pipe and fittings.

7.

DO NOT thread

pipe too far. Valve distortion

or

malfunction

may

result

from

excess

pipe

within

the

control.

Use

pipe

joint

compound

resistant

to

the

action

of

Liquified

Petroleum

gases

on

male threads

only.

DO NOT use

Teflon

tape. See illustrations below.

LEKGTH OF STANDARD PIPE THREADS (Indus)

EFFECTIVE

OVERALL

PIPE SIZE

LENGTH

LENGTH

OF THREAD

OF THREAD

3/8

3/8

9/16

1/2

1/2

3/4

3/4

1/2-9/18

13/16

1

9/16

1

CHECKING THE GAS PIPING

Ua£UCa!££E±SZ!£l

T

h

IT

a

OS*^^ COWTgpL use

moospats

amount

or oors

THREAD

rirc aiOHT CCNGTH bXAVf I SNO THNSADS SAfIS

8.

Refer

to

Figure

8

for

Gas

Pipe

sizes

for

natural

gas.

If

more than one appliance Is supplied from a single line size,

capacity

must

equal

or

axcaed

the

combinad

input

to

all

appliances,

and

the

branch

lines

feeding

the

individual

appliances properly sized for eech input.

Before

turning

gas

under

pressure

into

piping,

all

openings

from

which

gas

can

eacape

should

be

closed.

IMMEDIATELY

AFTER

TURNING

ON

GAS,

the

system

should

be

checked

for

leaks.

This

can

be

done

by

watching

the

1/2

cubic

foot

test

dial

and

allowing

S

minutes

to

show

any

movement,

and

by

soaping

each

pipe

connection

and

watching

for

bubbles.

If

a

leek

is

found,

make

the

necessary

repairs

immediately

and

repeat

the

above

test.

The

furnace

must

be

isolated

from

the

gas

supply

piping

system

by

closing

the

manual

shutoff

valve

on

the

combination

gas

control

valve

during

pressure

testing

of

the

gas

supply

piping

system

at

pressures

up

to

1/2

psig.

The

furnace

must

be

disconnected

from

supply

piping

and

supply

piping

capped

during

sny

pressure

testing

of

supply

piping system at test pressures in excess of 1/2 psig.

Defective

pipes

or

fittings

should

be

replaced

and

not

repeirad.

NEVER

USE

A

FLAME

OR

FIRE

IN

ANY

FORM

TO

LOCATE CAS LEAKS, USE A SOAP SOLUTION.

Advertising