Mls-3, mls-3ex level switches, Wiring details – Babbitt Liquid Level Gauge User Manual

Page 8

Advertising
background image

MLS-3, MLS-3EX LEVEL SWITCHES

DESCRIPTION

The MLS-3 and MLS-3EX are electrically the same, the EX version comes with an explosion proof
housing with terminal block. The MLS-3 switch is a hermetically sealed Bi-Stable latching reed
switch with SPDT Form C contacts. The switch is actuated by the float and latches, thus
maintaining the contact after the float continues to rise or fall with level. The MLS-3 is best suited
for low power alarm signals.

SPECIFICATIONS

Deadband:

.50 Inches

Max. Temperature:

650°F – HT Version
350°F – STD Version

Min. Temperature:

-40°F

Contacts:

Form C SPDT

Maximum Ratings:

Switching Voltage:

150 Volts AC/DC

Current:

1.0 Amps AC/DC

Power:

25 Watts DC/VA

SWITCH OPERATION/MOUNTING

To mount the MLS Series Level Switch simply clamp it directly to the side of the level gage
chamber using the adjustable pipe clamps provided. Alarm set points may be changed by simply
loosening the clamps and sliding the switch to the desired alarm level. To set up desired starting
state follow the steps below:

WIRING DETAILS

RISING LEVEL ALARM

MLS-3

Yellow

Green

Red

Green

MLS-3EX

A(NC)

C

B(NO)

C

FALLING LEVEL ALARM

MLS-3

Red

Green

Yellow

Green

MLS-3EX

B(NC)

C

A(NO)

C

Advertising