Connecting to valve – Bimba SPCS User Manual

Page 4

Advertising
background image

2014.01.23 rev4

4

1. Connecting to Valve

“With the air supply and power turned off”

1. Connect the SPCS-2 to the Bimba position feedback cylinder using cable SPCS-CBL-FBK.

2. If required, remove the top from the SPCS and configure internal jumper as shown in the illustration

below.

3. Connect the SPCS-2 to your power and command sources using cable SPCS-CBL-PWR-CMD.

4. Connect Pneumatic Lines.

a. Connect port 2 of the SPCS-2 to the back of the cylinder and port 4 to the front.

(3/8” O.D. tubing – 10’ or less length is recommended to prevent performance loss)

b. Inlet air should be dry (-40° F dew point) non-lubricated air, non-flammable & non-corrosive dry

gases (0.3 micron fine grade coalescing filter with 5 micron pre-filter) at 0-150psig.

c. Connect Inlet air to Port 1.

Power/Command & Feedback Connectors

Cable: SPCS-SBL-FBK

Cable: SPCS-CLB-PWR-CMD

5. Connect the valve to your computer using USB cable SPCS2-USB-CBL.

6. Must use a coalescing filter.