Dunkirk H2OI Stainless Steel Dual Coil Solar Water Heaters User Manual

Page 8

Advertising
background image

8

C. Locating the water heater.

The water heater should be located in an area where water leakage from the tank or connections will not result in damage

to areas adjacent to the water heater or to lower floors of the structure. When such a location can not be avoided, a suit-

able drain pan must be installed under the water heater, and the drain pan must be connected to a drain.
The water heater should be installed as close to the boiler as is practical for easy access for service. The unit is designed

for installation on combustible flooring and in alcoves, closets, etc.

The minimum clearances from combustible surfaces are:

Bottom -------------------------------- 0”
Left, right, and rear sides ---------- 0.5”
Front -------------------------------- 0.5”
Top ------------------------------------ 6”

The minimum clearances for service are:

Bottom -------------------------------- 0”
Left, right, and rear sides ------------ 3”
Front ----------------------------------- 6”
Top ------------------------------------ 6”

D.

Additional recommended components

1.

Shut-off valves. Allows the isolation of the water heater from the boiler system during service.

2.

Unions. Allows for easy locating or removal.

3.

Vacuum breaker. Protects the water heater from collapse if a hot tank is valved off to service other components

in the system.

4.

Thermal expansion tank. If the water heater is installed in a closed water supply system, such as a system

having a back flow preventer in the cold water supply line, the installation of a thermal expansion tank is

required.

E.

Removing the Existing Domestic Water Heating System

1.

External Tankless Heater- Disconnect all lines to the boiler and plug the boiler fittings. Disconnect the external

heater from the boiler piping, and the domestic piping systems.

2.

Internal Tankless Heaters- Disconnect the domestic piping. Do not plug the cold water or the hot water fittings

in the internal tankless coil. Leave the coil in the boiler with the cold and hot water fittings open to prevent

pressure build-up in the coil.

WALLS

W

ALLS

CEILING

6" Minimum

0.5" Minimum

0.5"
Min.

Sides

0.5"
Min.

Sides

0.5"
Min.

Sides

0.5"
Min.

Sides

Top

Rear

Front

Provide access clearance

Front View

Top View

Advertising