The Node Object implements the following configuration properties:

Configuration Property

Description

SCPTmajDevVer

Defines the major version of the device, and can be
useful for integrators when upgrading or verifying
installations. This property is read-only.

SCPTminDevVer

Defines the minor version of the device, and can be
useful for integrators when upgrading or verifying
installations. This property is read-only.

UCPTfactoryDefaultsEnable If set to True (the default), an end-user can use the

Monitor Service button to reset the MPR-50 to factory
defaults. To prevent tampering with the configuration
of the MPR-50 from the front panel, disable this
feature by setting the configuration property to False.

UCPTrepeaterModeEnable

If set to True (the default), an end-user can use the
Monitor Service button to put the MPR-50 into
repeater mode. To prevent tampering with the
configuration of the MPR-50 from the front panel,
disable this feature by setting the configuration
property to False.

Error Log

Certain network variables that are part of the Channel Monitor functional blocks are

alarmed, and the Monitor maintains an error log of any alarm conditions. The log is

circular, the entries are in the SNVT_alarm_2 format, and it contains up to 50 of the

latest alarms. Think of this error log as the latest 50 values that have been output

on the Node Object's nvoAlarm2 output. The error log is not retained across power

cycles or resets.

A network management tool can read this error log using standard L

ON

M

ARK

direct

memory read/write commands, and use the error log contents to aid in debugging

network problems. The network management tool uses the nvoFileDirectory

network variable to find the location of the error log. LNS based tools can use the

available LNS FileTransfer method to transfer the log file. For instance, when using

LonMaker Turbo Edition, choose LonWorks FTP… from the LonMaker menu. When

not using an LNS based tool, see the Node Object Functional Profile and the

L

ON

M

ARK

Application Layer Interoperability Guidelines on the L

ON

M

ARK

Web site

for details about how to read the log file.

The index of the log file in the Monitor is 3. The format of the error log is as follows:

26