• Ch<n>: Bandwidth (xx%)

In the L

ON

M

ARK

guidelines, the possibility exists for two limit levels (levels 1 and 2)

for each of the low and high limits. The MPR-50 implements a single limit according

to the following rules:
1. If the alarm type was not AL_HIGH_LMT_ALM_1 and the value is now greater

than SCPThighLimit1, then the alarm type becomes AL_HIGH_LMT_ALM_1.

2. If the alarm type was AL_HIGH_LMT_ALM_1 and the value drops below

SCPThighLimit1

minus SCPThystHigh1, then the alarm type becomes

AL_HIGH_LMT_CLR_1

. For high limit alarms, the hysteresis value is used only to

subtract from the limit value.

3. If the alarm type was not AL_LOW_LMT_ALM_1 and the value is now less than

SCPTlowLimit1

, then the alarm type becomes AL_LOW_LMT_ALM_1.

4. If the alarm type was AL_LOW_LMT_ALM_1 and the value rises above

SCPTlowLimit1

plus SCPThystLow1, then the alarm type becomes

AL_LOW_LMT_CLR_1

. For low limit alarms, the hysteresis value is used only to

add to the limit value.

The nvoIvalCrcErr and nvoIvalMissed variables have a high alarm limit
(SCPThighLimit1) and do not have a low alarm limit. A hysteresis value
(SCPThystHigh1) is used to prevent oscillation of the alarm condition when it is
near the high alarm limit value. The high alarm is enabled by default via the
SCPThighLimit1Enable

property.

The nvoIvalBandUtl variable has both a high alarm limit (SCPThighLimit1) and
a low alarm limit (SCPTlowLimit1). The high alarm is enabled by default via the
SCPThighLimit1Enable

property, and the low alarm limit is disabled by default

via the SCPTlowLimit1Enable property. The low alarm limit can be useful to
detect that, for instance, a certain level of background heartbeat traffic expected on a

channel has slowed or stopped—which indicates a power, channel wiring, or other

problem. If the low alarm limit is enabled, also set the SCPTlowLimit1 property to
a non-zero value that is slightly below the expected level of background heartbeat

traffic. Hysteresis values (SCPThystHigh1 and SCPThystLow1 as appropriate) are
used to prevent oscillation of the alarm condition when it is near the alarm limit

value.