Troubleshooting Table

This troubleshooting table is intended to address abnormal operation only and does not

include errors reported on the Status LEDs. Refer to the LED Legends section in Chapter

2 for a description of the Status LED messages.

Symptom

Troubleshooting Solutions

The Power LED is not on continuously.

• Verify that the input voltage measured

at the MPR-50 power input connector is

within limits.

• Verify that the input power is connected

to terminals 1 and 2.

• Remove the earth ground connection

temporarily if it is connected.

A network tool does not receive a service pin

message when the Monitor’s Service button

is pressed.

• Verify that Service pin messages from

other devices can be received.

• Verify that the router inside the MPR-50,

in between the Monitor and the network

tool, has been commissioned properly by

the network tool or is in repeater mode.

• Verify that the network wiring is

functional by pressing the Service button

on any intervening routers, and on the

router inside the MPR-50, in between the

Monitor and the network tool.

• Verify that the proper transceiver types

are connected to a particular channel.

For instance, verify that a TP/FT-10

channel is not connected to the Router 1

– TP/XF-1250 port of the MPR-50, and

that a TP/XF-1250 channel is not

connected to Routers 2-5.

• Verify that the network channels are

properly terminated with either a single

or double termination, as required.

• If the configuration of Routers 1–5 is in

doubt, put it into repeater mode. Then

press the Service button on the Monitor.

The network tool returns error messages

when attempting to install Routers 1–5 and

the Monitor in a single operation.

• First commission only the router nearest

to the network tool. Then commission

the other routers and the Monitor at the

same time.

32

Troubleshooting