Chapter three – Heath Consultants Aqua-Scop User Manual

Page 22

Advertising
background image

IV. AQUA-SCOPE USER’S GUIDE:

A. Application

The pinpointing of unknown water leakage can be accomplished

by the use of a combination of components, which make up the

kit. By using different microphones and by amplification with

a solid-state receiver, the sounds of water leaking from the line

can be localized and pinpointed. The type or pitch of the sound

varies from the deep roaring of a main up to a very high whining

of leaking valve packing. It is necessary to differentiate these

sounds from the other normal background noises.

Auxiliary Means - Plunger Bar: Useful when searching for leaks

on soil or sod covered pipes. Surfaces of this nature are poor

sound transmitters and require the use of a bar as an auxiliary

sounding.

Resonant Plate: The Resonant Plate is a specially machined

plate, which improves the sounding qualities. The Plate is

designed to accept the Ground Microphone.

B.

Leakage Detection with the Direct Contact Microphone

Preliminary Detection with the Direct Contact Microphone:

The Direct Contact Microphone is used for preliminary detection

in direct contact with an accessible part of the main, hydrant,

curb valves, or directly on the service in the house, etc. The

intensity of this direct contact is always in direct relationship

to the distance of the leak from the point of measurement and

indicates where the leak might be. By acoustic comparison of

the noise heard in the Headset and by visual observation of

the noise strength with the aid of the optional meter readout

module at one or more points of measurement, the leak can be

approximately located.

19

CHAPTER THREE

Advertising