Instance ID 2 (position control)

NOTE:

There is no subclass

for instance 2

TAbLE 8.11.2 – S-SINGLE STAGE CONTROLLER ObJECT ATTRIbUTES; INSTANCE 2

attrIBute Id

hex

ServIce Id

HEx

name

Format

value

3

0E (get) 10 (set)

Data type

USINT

C3h = INT (default)
CAh = Real

4

0E (get) 10 (set)

Data units

UINT

1001h = Counts (default
1007h = Percent
1703h = Degrees

5

0E (get) 10 (set)

Control Mode

USINT

See table 8.11.3

6

10 (set)

Setpoint

UINT

Specified by data type

7

0E (get)

Process

variable

(Position)

Specified by

data type

Analog output value
Linked to S-Analog Sensor
Object, instance 3

9

OE (get) 10 (set)

Control

variable

Specified by S-

Analog Actuator

Object data type

Drive signal output
Linked to S-Analog
Actuator Object, instance 1
0000h - 7FFFh

0A

0E (get)

Status

BYTE

See table 8.11.4

11

OE (get) 10 (set)

Safe State

USINT

See table 8.11.5

TAbLE 8.11.4 – S-SINGLE

STAGE CONTROLLER ObJECT

STATUS bITmAP

BIt

deFInItIon

0

Alarm exception
0 = cleared, 1 = set

1

Warning exception
0 = cleared, 1 = set

2-7

Reserved

8.11 - S-Single Stage Controller Object

(continued)

TAbLE 8.11.3 – S-STAGE CONTROLLER

ObJECT CONTROL mODE vALUE

attrIBute

value

State

0

Normal

1

Closed

2

Open

3

Hold

4

Safe State (Closed)

5-63

Reserved

TAbLE 8.11.5 – S-SINGLE STAGE

CONTROLLER ObJECT SAFE STATE vALUE

attrIBute

value

State

0

Closed

1

Open

2

Hold (Default)

3

Safe Value - Closed

4-63

Reserved