Calculated Probe Set up

Inject the picofarad equivalent
of maximum level from line 11 of the
worksheet. Watch the probe loading LED:

LED is on — close DIP switch

1 and go to step 2.

LED is off — go to step 3.

LED is on — close DIP switches

1 & 2 and go to step 3.

LED is off — go to step 3.



Turn the span pot CW until the probe

loading LED lights, and then CCW to

the point where the LED goes off.

Slowly cycle the LED on and off
as required to find the precise threshold
at which the LED goes off.

 Turn all set point adjust pots

fully CCW (25 turns CCW).
 Turn all on and off delay pots

fully CCW (one turn pots).
 Set all fail safe switches to
LO

position.

Continue with Calculated set point set up
on the page which matches the first three
digits of the model number.

661.......p. 14
662.......p. 16
663.......p. 18
664.......p. 20
665.......p. 22
666.......p. 24
667.......p. 26
668.......p. 28

3000pf

2200pf

5200pf

4450pf

L

700pf

Solve for pf/ft.

Solve for pf/1 ft.

Level A 10’ 2200pf
-Level B -8’ -1900pf
pf /ft. 2’ = 300pf

pf 300 =150pf/ft.
ft. 2

30’

25’

20’

15’

10’

5’

0’

30’

25’

20’

15’

10’

5’

0’

30’

25’

20’

15’

10’

5’

0’

30’

25’

20’

15’

10’

5’

0’

30’

25’

20’

15’

10’

5’

0’

Solve for C in ft.

Convert C to pf

Max Level 30ft.
-Level A -10ft.
C 20ft.

C 20ft.
x pf/ft. x150pf
C in pf 3000pf

Solve for Max Level in pf

C 20’ = 3000pf
+Level A + 10’ = 2200pf
Max Level 30’= 5200pf

Solve for H in pf

Solve for pf @ Zero ft.

Max Level 30ft.
x pf/ft. x 150pf
H 4500pf

Max Level (pf) 5200pf
-H -4500pf
pf @ Zero ft. 700pf

Set point 25ft.
x pf/ft. x 150pf
L 3750pf

L 3750pf
+ Zero ft. + 700pf
Set point 4450pf

C=20’

Convert Set point to pf

Add zero value to L

5200pf

H

700pf

ft