For set point 4, For the adjustable differential set point, Time delay adjustments – SOR Multi Point RF Level Switch User Manual

Page 27

Advertising
background image

Form 677 (05.13) ©SOR Inc.

27/36

For set point 4:

LO mode: When the set point is satisfied, the relay turns on. When process level falls below
the set point, the relay turns off and remains off until the set point is once again satisfied.
HI mode: When the set point is satisfied, the relay turns off. When process level falls below
the set point, the relay turns on and remains on until set point is once again satisfied.

For the adjustable differential set point:

LO mode: When the upper limit is satisfied, the relay turns on. When process level falls below
the lower limit, the relay turns off and remains off until the set point is once again satisfied.
HI mode: When the upper limit is satisfied, the relay turns off. When process level falls below
the lower limit, the relay turns on and remains on until the upper limit is once again satisfied.

Switch

Position

Set Point

Status

Relay

Coil

Relay Continuity

Failsafe

LO/HI

OFF

ON

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

NC1 C1 NO1 NO2 C2 NC2

ON

OFF

Failsafe

LO/HI

Set
Point

Set
Point

Set
Point

Set
Point

Time Delay Adjustments

Set point 4 may be equipped with time delay adjustments. Both on delay and off delay are
one turn pots.
On Delay: Length of time that set point must be satisfied before the output relay reacts.
Off Delay: Length of time that process must be below set point before the output relay reacts.
Adjustment pot fully CCW = 0-second delay
Adjustment pot fully CW = second delay (approximate)