Form 677 (05.13) ©SOR Inc.

Adj
Diff

Set
Point 4
Terminals

Set
Point 1
Terminals

UPPER

LIMIT

RELAY

FAIL SAFE

LOWER

LIMIT

SPAN

RANGE

RELAY
FAIL SAFE

TIME DELA

Y

OFF

ON

LEVEL

ADJUST

ABLE DIFFERENTIAL SET POINT

Set Point 4

Adjust

*Presence LED

*On Delay

*Off Delay

Relay On LED

Fail-safe Hi/Lo

Upper Limit

Presence LED for
Upper Limit

Relay ON LED

Failsafe Hi/Lo

Lower Limit Adjust

Presence LED for
Lower Limit

Set Point 1

Adjust

*Presence LED

*On Delay

*Off Delay

Relay On LED

Fail-safe Hi/Lo

*When the time delay option
is not
specifi ed:

Relay On LED functions as
Starred parts not supplied

Adj
Diff

Set

Point 2

Adj. Diff

Terminals

Model 668 Set Point Set up and Output Wiring

Actual Level set point set up

Continued from page 8.

Process level must be steady at set point 1 level. Turn set point 1 adjust pot CW until its
Presence LED lights and then CCW to the point where the LED goes off. Slowly cycle the
Presence LED on and off as required to find the precise threshold at which the LED goes off.
 Lower process level to upper limit of the adjustable differential set point. Use the upper

limit (pump up) adjust pot to find the threshold of its Presence LED.

 Lower process level to lower limit of the adjustable differential set point. Use the lower

limit (pump down) adjust pot to find the threshold of its Presence LED.

 Lower process level to set point 4 level. Use the set point 4 adjust pot to find the

threshold of its Presence LED.

Continue with output wiring from the right side of this page.

Calculated set point set up

Continued from page 9.

The pf value from worksheet line 11 should still be injected. Turn set point 1 adjust pot CW
until its Presence LED lights and then CCW to the point where the LED goes off. Slowly
cycle the LED on and off as required to find the precise threshold at which the LED goes off.
 Inject the pf value from line 15 of the worksheet. Use the upper limit (pump up) adjust

pot to find the threshold of its Presence LED.

 Inject the pf value from line 17 of the worksheet. Use the lower limit (pump down)

adjust pot to find the threshold of its Presence LED.

 Inject the pf value from line 19 of the worksheet. Use the set point 4 adjust pot to find

the threshold of its Presence LED.

Disconnect the probe lead and the probe ground lead from the capacitor substitution box
terminals. Connect the probe lead and the probe ground lead to the probe. Continue with
output wiring from the right side of this page.