Micro800™ 2 Ch High Current Digital Output Module

14 

Publication 0100188-01 Rev. A

Environmental Tests

Industry Standards

Test Level Limits

EFT/B immunity

IEC 61000-4-4*

Signal Ports:

± 3 kV @ 5 kHz for 5 minutes

Power Ports:

± 2 kV @ 5 kHz for 5 minutes

Surge transient immunity

(Performance Criteria B)

IEC 61000-4-5

Signal Ports:

± 2 kV line-earth

Power Ports

± 2kV CM

± 1kV DM

Conducted RF immunity

(Performance Criteria A)

IEC 61000-4-6

10V rms with 1 kHz sine wave
80%AM from 150 kHz…80 MHz
on signal and power ports

Magnetic Field

(Performance Criteria A)

IEC 61000-4-8

30Arms/m

AC Mains Voltage Dips,
Interruptions and Variations

IEC 61000-4-11

Standard

Safety Tests

Industry Standards

Test Level

Limits

UL Safety

UL 508 Industrial Control Equipment Seventeenth
Edition Dated January 28 1999, with revisions
through July 11, 2005 (ANSI/UL 508-
2005) (NRAQ, NRAQ7)

cUL CSA C22.2 No. 142 -M1987 Process Control
Equipment May 1987

As required

UL Hazardous Locations

ULH ANSI/ISA–12.12.01–2007 Nonincendive
Electrical Equipment for Use in Class I, Division 2
Hazardous (Classified) Locations

cULH CSA C22.2 No. 213-M1987 - Non-
incendive Electrical Equipment for use in Class I
Division 2 Hazardous Locations - March 1987

As required

CE Low Voltage Directive

IEC 61131-2 Programmable Controllers Part 2:
Equipment Requirements and Tests; Second
Edition 2003-02, Section 11-14

As required

Micro800™ 2 Ch High Current Digital Output Module

Publication 0100188-01 Rev. A

Wire the Module

Follow the wiring diagrams below to wire the module.

Note: In the diagram above, terminals with the same label are internally shorted together.
Example, CM0 (Top Row) and CM0 (Bottom Row) are internally shorted together.

Configuring the Module

The 2080sc-OW2IHC doesn’t really require configuration. It only needs
to be placed into run mode. Write a value of 165 decimal to memory
location 17 (MOD_MODE_CONTROL). See Table 3 for more
information.

Micro 800 controllers running OS firmware
revision 1.12 or older, require a decimal value of
16 be written to memory location 11
(CONTR_OPS_STATUS) before the module will
go into run mode. See program sample on
page 9.

Module Input Data

General module status can be read from memory location 16. Refer to
table below for possible responses.

Table 1 (General Module Status)

Bit Number

Description

0-1

These 2 bits define module operation mode,
0: Idle: Module is ready to RUN, and I/O is off.
1: RUN: Module is under RUN, and I/O is on.
2: Error: Error happens, and I/O is off.
3: Busy: Module is busy, cannot go to RUN, and I/O is off.

CM0

O-0

NC

NC

CM1

O-1

CM0

O-0

NC

NC

CM1

O-1

L2

or

-DC

L2

or

-DC

L1

or

+DC

L1

or

+DC

Load

Load