Table 4(controller operation status register), Table 5 (ccw program variables) – Spectrum Controls 2080sc-OW2IHC User Manual

Page 9

Advertising
background image

Micro800™ 2 Ch High Current Digital Output Module

12 

Publication 0100188-01 Rev. A

Minimum Load

10mA at 5VDC per point.
(This value can change due to the switching frequency, environmental conditions, and desired
reliability level, therefore it is recommended to check this with the actual load.)

Initial Contact
Res. of Relay

< 5mΩ typical, 30 mΩ max

Expected Life
of
Electrical
Contacts

100k operations @ 20 times/min, at rated resistive capacity and temperature.


Switching
Frequency

Maximum 1 cycle /3s at rated load (1.5s on, 1.5s off)

Bounce Time

1.2 ms average

Maximum Off
State Leakage

1.5mA Maximum

Output Delay
Time
(From the time
the module
receives data)

10ms maximum on/off (5 ms typical) excluding bounce time

Status
Indicators

2 yellow Status Indicators (I/O)

Power source

3.3 VDC, 24 VDC from backplane

Input to
backplane
isolation

250 VAC continuous, tested at 2300VAC for 1 min.

Channel to
channel
isolation

250 VAC continuous, tested at 1500VAC for 1 minute

Power
consumption

<=35 mA at 3.3V, <=20 mA at 24V, <1.5 W

Inrush current

<120 mA at 3.3V, <120 mA at 24V

Fusing

Use external if desired

Terminal block
Wire size

#16 - #30 AWG

Terminal block
torque

0.19 Nm (1.7 lb-in)

Mounting
torque

0.2 Nm (1.48 lb-in)

Manufacturing RoHS

compliant

Dimensions

58.4mm x 29.3mm x 25mm

Status
Indicators

Individual OFF/ON Status for each I/O point

Micro800™ 2 Ch High Current Digital Output Module

Publication 0100188-01 Rev. A

Parameter

Offset

(Dec) Comments

MOD_MODE_CONTROL

17

Module Mode Control Register

OUTPUT_DATA 64 Output

Data

Register

Table 4(Controller Operation Status Register)

Bit Number

Description

0-3

Controller Error info:
0x00: no Error;
0x01: Operation Error;
0x02: Fatal Error
0x03-0x0F: reserved ;

4-5 Controller

mode:

0x00: non-RUN mode;
0x01: RUN mode;
0x02-0x03 : reserved ;

6-7

Controller Power info:
0x00: Power O.K.;
0x01: power failure triggered;
0x02-0x03: reserved

The following sample program, written in structured text, demonstrates
how to configure the module in CCW.

u800Slot := 1; (* Slot number for module. *)

(* This section of code is to handle the controller with Firmware earlier than rev 1.13 *)
SYS_INFO_FW(True);
IF (SYS_INFO_FW.Sts.OSMajRev = 1 and SYS_INFO_FW.Sts.OSMinRev <=12) THEN
IF SYS_INFO_FW.Sts.MajErrCode = 0 THEN
ControllerStatus[1] := 2#00010000;
WriteControllerStatus(True,u800Slot,11,1,ControllerStatus);
END_IF;
END_IF;

RunMode[1] := 16#A5;

(* Initialize RunMode register *)

WriteModModeControl(true,u800Slot,17,1,RunMode); (* Write A5 Hex to MOD_MODE_CONTROL for run mode*)
ReadModStatus(true,u800Slot,16,1,OW2IHC_S1_ModStatus);

(* Read general module status *)

WriteOutputs(True,u800Slot,64,1,OW2IHC_S1_Outputs); (* Write Output states *)

Table 5 (CCW Program Variables)

Variable Name

Data Type

Dimension

U800Slot UINT

NA

SYS_INFO_FW SYS_INFO

NA

ControllerStatus USINT

[1..1]

WriteControllerStatus Plugin_Write

NA

WriteModModeControl Plugin_Write

NA

RunMode USINT

[1..1]

ReadModStatus Plugin_Read

NA

OW2IHC_S1_ModStatus USINT

[1..1]

WriteOutputs Plugin_Write

NA

OW2IHC_S1_Outputs USINT

[1..1]

Advertising