Module output data, Adding the ow2ihc to ccw, Environmental specifications – Spectrum Controls 2080sc-OW2IHC User Manual

Page 8

Advertising
background image

Micro800™ 2 Ch High Current Digital Output Module

Publication 0100188-01 Rev. A

Module Output Data

The two output channels on the OW2IHC are controlled by memory
location 64, bits 0 and 1 control channels 0 and 1 respectively. See
Table 3 for memory location offsets. The table below describes the state
of each output channel in relation to the control bits.

Table 2 (Output States)

Channel # Bit state Output State

0

0 OPEN

1 CLOSED

1

0 OPEN

1 CLOSED

Adding the OW2IHC to CCW

The 2080sc-OW2IHC is configured for CCW (Connected Components
Workbench) using the PLUGIN_READ and PLUGIN_WRITE instructions
for generic plug-in modules.

The configuration, output data, and status structures discussed in the
sections above, are stored at different memory locations in the module.
The following table lists the memory location offset for each parameter
which is used when configuring the PLUGIN_READ, WRITE, and INFO
instructions.

Table 3 (Parameter Offset)

Parameter

Offset

(Dec) Comments

MOD_ID_LO 0 Module

ID

MOD_ID_HI 1
VENDOR_ID_LO 2

Vendor

ID

VENDOR_ID_HI 3
PRODUCT_TYPE_LO 4

PRODUCT_TYPE_HI 5

PRODUCT_CODE_LO 6

PRODUCT_CODE_HI 7

MOD_REV_LO

8

Minor revision, 1-255

MOD_REV_HI

9

Major revision, 1-127

CONTR_OPS_STATUS

11

Controller operation status information

(see Table 4)

MOD_STATUS

16

Module status register

(see

Table 1)

Micro800™ 2 Ch High Current Digital Output Module

13 

Publication 0100188-01 Rev. A

Environmental Specifications

Environmental Tests

Industry Standards

Test Level Limits

Temperature (Operating)

IEC60068-2-1: (Test Ad, Operating Cold),

IEC60068-2-2: (Test Bd, Operating Dry Heat),

IEC60068-2-14: (Test Nb, Operating Thermal Shock)

-20 to 65°C (-4 to 149°F)

Temperature

(Non-operating)

IEC60068-2-1:

(Test Ab, Unpackaged Non-operating Cold),

IEC60068-2-2:

(Test Bb, Unpackaged Non-operating Dry Heat),

IEC60068-2-14:

(Test Na, Unpackaged Non-operating Thermal Shock)

-40 to 85°C (-40 to 185°F)

Operating Altitude

2000 meters (6561 feet)

Not tested

Humidity (Operating)

IEC60068-2-30:

(Test Db, Unpackaged Damp Heat):

5 to 95% non-condensing

Vibration (Operating)

IEC60068-2-6: (Test Fc, Operating)

5G

Shock (Operating)

IEC60068-2-27: (Test Ea, Unpackaged Shock)

10 g

Shock (Non-operating)

IEC60068-2-27: (Test Ea, Unpackaged Shock)

50 g

Radiated Emissions

CSIPR 11; Group 1, Class A

30MHz – 1GHz

Conducted Emissions

IEC 61000-6-4:2007
Group 1, Class A (AC Mains)

150kHz – 30MHz

ESD immunity

IEC 61000-4-2

4kV Indirect (Coupling Plate)

4kV Contact Discharge (to points
of initial contact)

8kV Air Discharge (to points of
initial contact)

Radiated RF immunity

IEC 61000-4-3: Level 3

10 V/M with 1 kHz sine-wave
80%AM from 80…2000 MHz

10 V/M with 200 Hz sine-wave
50% Pulse 100%AM @900 MHz

10 V/M with 200 Hz sine-wave
50% Pulse 100%AM @1890 MHz

3 V/M with 1 kHz sine-wave
80%AM from 2000…2700 MHz

Advertising