Table 4-15 Ladder Get Device Information (Service Code = 0×4D)

Unconnected Message

Field

Value

Definition

Message Type

CIP Generic

Service Code

0×4D

Get Device
Information

Class Name

0×035D

HART Object

Instance Name

1 no n

Selects channel n-1

Object Attribute

None, leave this field blank

Request Size

0

No Request Data

Reply Size

2-120 bytes
(2) Size when Device information not
available
(120) Size when valid Device Information
returned

Number of Data
bytes returned

Request Data
HART Get Device Information - Request packet structure
Request Size = 0
Offset Field

Value

Definition

No Request Data

Request Failed Response
HART Get Device Information - Reply packet structure
Reply Size = 2

Offset Field

Value

Definition

0

Status

34 = DR_RUNNING
35 = DR_DEAD

Command status

1

Pad

0

Pad byte

Request Succeeded Reply
HART Get Device Information - Reply packet structure
Reply Size = 120 bytes

Offset

Field

Value

Definition

0

Status

00 = SUCCESS

Command status

1

HARTManufID_EdtMSB

(1 byte)

CMD#0, Byte 1

2

HARTDeviceType_EdtLSB

(1 byte)

CMD#0, Byte 2

3

HARTPreamble

(1 byte)

CMD#0, Byte 3

4

HARTUnivCmdCode

(1 byte)

CMD#0, Byte 4

5

HARTTransSpecRev

(1 byte)

CMD#0, Byte 5

6

HARTSoftwareRevision

(1 byte)

CMD#0, Byte 6

7

HARTHardwareRevision

(1 byte)

CMD#0, Byte 7