Spectrum Controls 1734sc-OE2CIH User Manual

Page 69

Advertising
background image

Appendix A: Configuration Information

A-3

User’s Manual Pub. 0300272-01 Rev. A.0

Table A-2 Safety Tests and Test Limits

Safety Tests

Industry Standards

UL Safety

UL 508 Industrial Control Equipment Seventeenth Edition Dated January 28 1999, with
revisions through July 11, 2005 (ANSI/UL 508-2005) (NRAQ, NRAQ7)
cUL CSA C22.2 No. 142 -M1987 Process Control Equipment May 1987

UL Hazardous Locations

UL ANSI/ISA–12.12.01–2007 Nonincendive Electrical Equipment for Use in Class I,
Division 2 Hazardous (Classified) Locations T4 or better
cULH CSA C22.2 No. 213-M1987 - Non-incendive Electrical Equipment for use in
Class I Division 2 Hazardous Locations - March 1987

CE Low Voltage
Directive

IEC 61131-2 Programmable Controllers Part 2: Equipment Requirements and Tests;
Second Edition 2003-02, Section 11-14

European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15:2010; Potentially Explosive Atmospheres, Protection
II 3 G Ex nA IIC Gc DEMKO 13 ATEX 1214881U
EN 60079-0:2012; General Requirements (Zone 2)


Table A-3 Performance Requirements

Number of Outputs

Two Isolated Outputs

Configuration

Defined by configuration word

Output ranges

0 to 20 mA and 4 to 20 mA (HART available only on 4-20 range)

Output load

0 to 750 ohms max; 200 to 750 ohms for HART

Resolution

16 bits across 21 mA to 320 mA

Data format

Signed Integer

Conversion type

R ladder DAC

Full scale settling time

<100 ms to 95% with resistive loads

Differential nonlinearity

±0.05% full scale

Output ripple

±0.05%, or better full scale 0 to 50 kHz

Repeatability (HART disabled) ±0.05% full scale

Max inductive load

(current outputs)

10 uH

Output impedance

>10 kohms at 1 kHz>1 k at 10 kHz; > 10 megaohms at DC

Accuracy

Range

Temperature

Accuracy (% Full Scale)

0 to 21 mA extended 25°C

0.15% FS

0 to 21 mA extended -20°C to 55°C

0.30% FS

Long term drift

Power on/off channel glitch

Under ±1 V for 2 ms or ±2.5V for 400 uS. Target: ±0.5 V spike for less than 5 ms

Open and short circuit
protection

Yes, continuous. (IEC 1131-2 requirement)


Advertising