5. TROUBLESHOOTING

: The Surge + Diagnostic

and Data Interface Cable contain no user-serviceable

parts. Do not attempt product disassembly, as this will void the product warranty.

5.1 Surge + Diagnostic

Symptom

Possible Cause

What To Do

Red LED On, Green LED Off, No
power at output.

Incorrectly wired branch
circuit outlet. The LCD Event

Monitor will display the nature
of the wiring fault.

Contact a licensed electrician to correct the branch circuit
outlet wiring.

Red LED Off, Green LED Off, No

power at output.

No voltage or unacceptable

voltage at branch circuit
outlet, or Surge + Diagnostic

output manually turned Off.

If the LCD Event Monitor is not on, there is no power at

the wall receptacle. If the voltage is unacceptable, the
LCD Event Monitor will display the type of voltage

condition. Use the Diagnostic Software to measure the
voltage at the wall receptacle. Contact a licensed
electrician to troubleshoot the wall receptacle. Use the

Diagnostic Software to manually turn the outlets On.
Alternately, press and release the RST button once to

manually turn the outlets On.

Red LED Off, Green LED On, No
power at output.

Defective product.

Contact ESP for product replacement at 800.645.9721.

5.2 Diagnostic Software

Symptom

Possible Cause

What To Do

Receive error related to .ocx or .dll
file when attempting to start

software.

ActiveX control not installed.

Refer to Section 2: Installation
Instructions/Diagnostic Software Installation

and Section 4: Diagnostic Software for
instructions on re-installing the Surge +
Diagnostic Software.

Part of the program screen is not
visible on the computer monitor.

The computer’s screen resolution is set too
low.

Set the computer’s screen resolution to a
minimum of 1024x768.

Software will not connect to Surge

+ Diagnostic.

Correct COM port is not selected, Surge +

Diagnostic Data Interface Cable is not
connected, Serial-USB drivers are not

installed, or Surge + Diagnostic Data
Interface Cable is connected to wrong port
on Surge + Diagnostic.

Verify all connections and

set the correct COM port, as detailed in
Section 2: Installation Instructions.

Software will not send email.

Email settings are incorrect, computer does
not have an internet connection, ISP blocks

outgoing SMTP communications.

Verify that email settings are correct. Verify
that the computer is connected to the

internet. Contact ISP regarding policies on
outgoing SMTP communications.