6. SPECIFICATIONS

Parameter

Specification

Load Rating

SX-HS-15-R

15 Amps at 120 Volts

SX-HS-20-R

20 Amps at 120 Volts

SX-HS-L530-R

30 Amps at 120 Volts

SX-HS-L630-R

30 Amps at 120/230 Volts Split Phase

SX-HS-L630-RDB

2 x 30 Amps at 120/230 Volts Split Phase

Voltage Protection Rating
(VPR)

SX-HS-15-R
SX-HS-20-R

330V All Modes

SX-HS-L530-R

Pending

SX-HS-L630-R
SX-HS-L630-RDB

800V Line-Line
500V Line-Ground

Attenuation

Normal
Mode

SX-HS-15-R
SX-HS-20-R
SX-HS-L530-R

SX-HS-L630-R
SX-HS-L630-RDB

> 30 dB 80kHz – 50MHz

Common

Mode

SX-HS-15-R
SX-HS-20-R
SX-HS-L530-R

> 30 dB 70kHz – 50MHz

SX-HS-L630-R
SX-HS-L630-RDB

> 30 dB 200 kHz – 50MHz

Power Requirement

(no load)

SX-HS-15-R
SX-HS-20-R

4 Watts

SX-HS-L530-R
SX-HS-L630-R

SX-HS-L630-RDB


6 Watts

Under-Voltage Shutdown

120V Models

Adjustable from 80V to 95 V, or Disabled. Restores at 105V.

208/230V Models

Adjustable from 140V to 170 V, or Disabled. Restores at 190V.

Over-Voltage Shutdown

120V Models

Adjustable from 135V to 160V. Restores at 130V.

208/230V Models

Adjustable from 260V to 300V. Restores at 250V.

Internal Memory Capacity

60 Events with timestamp; 999 counts of each event type

Timestamp Accuracy

± 2.5%

Voltmeter Accuracy
(Peak Reading Type)

120V Models

± 2% Typical product accuracy between 40V and 180V

208/230V Models

± 2% Typical product accuracy between 100V and 300V

Response Time

Over-Voltage

100 msec

Under-Voltage

150 msec

Under-Voltage Record
Definition

120V Models

AC Voltage has dropped below 100V

208/230V Models

AC Voltage has dropped below 180V

Over-Voltage Record
Definition

120V Models

AC Voltage has risen above 135V

208/230V Models

AC Voltage has risen above 260V

Power Outage Event Definition

AC Voltage has dropped below 20V

Surge Event Definition

Surge + Diagnostic

has been exposed to a transient voltage in one of the 3 possible

modes (between Live and Neutral, between Live and Ground, between Neutral and
Ground) with a peak amplitude of 500V-700V* or higher and a frequency of 20 kHz or
higher. *500V-700V surge voltage amplitude applies to IEEE C62.41 Category B
Impulse; surge voltage amplitudes necessary for detection of other surge types may
vary.