The aurora advanced vs control system cont, Aurora advanced vs control features, Control features – WaterFurnace 7 Series User Manual

Page 23

Advertising
background image

23

7 SERIES 50Hz 700A11 INSTALLATION MANUAL

Add On Control Feature Kits

(field or factory Installed)

Description

Aurora Advanced VS

Geo Energy Monitoring Kit

Monitors real time power consumption of compressor, blower, aux heat and pump.
Requires thermostat TPCM32U04 or TPCC32U01.

Standard

Refrigeration Monitoring Kit

Monitors real time pressures, temperatures, superheat, and subcooling.

Standard

Performance Monitoring Kit

Monitors air and water temperatures, and water flow rate and calculates heat of
extraction/rejection.

Optional Sensor Kit

Data Logging (AWL) Kit

Allows data logging of up to 12 months. Can also be temporarily installed.

Optional

HAN/Smart Grid Com

(AWL and Portal) Kit

Allows direct communication of the Aurora to Smart Meters, HAN, and internet.

Optional

Add On Thermostats and Zoning

Description

Aurora Advanced VS

TPCM32U04 - MonoChrome
Communicating Thermostat

Elite Stat with full English fault codes and alerts, communicating thermostat;
Required for viewing Energy Monitoring. Monochrome thermostat allows
instantaneous energy measurement only.

Optional

TPCC32U01 - Color Touchscreen

Communicating Thermostat

4.3 in. color touchscreen communicating thermostat with full English fault codes
and alerts; Required for viewing Energy Monitoring. Color thermostat allows
instantaneous and 13 month history.

Optional

IntelliZone2

®

Zoning

Includes color main thermostat and up to 6 zones (with variable speed), 4 zones
(with dual capacity), and 2 zones (with single speed). There are 3 thermostat
options (MasterStat, SensorStat, ZoneStat).

Optional

NOTES: The IntelliZone2 or one of the communicating thermostats shown above must be used to control the variable speed heat pump.

Aurora Advanced VS Control Features

NOTE: Refer to the Aurora Advanced VS Control Application

and Troubleshooting Guide and the Instruction Guide: Aurora

Interface and Diagnostics (AID) Tool for additional information.

Control Features

Software ABC VS Version 2.0 Variable Capacity Compressors

• Random start at power up

• Anti-short cycle protection

• High and low pressure cutouts

• Loss of charge

• Water coil freeze detection

• Air coil freeze detection

• Over/under voltage protection

• Condensate overflow sensor

• Load shed

• Dehumidification (where applicable)

• Emergency shutdown

• Diagnostic LED

• Test mode push button switch

• Two auxiliary electric heat outputs

• Alarm output

• Accessory output with N.O. and N.C.

• Modbus communication

Variable Speed ECM Blower Motor

A variable speed ECM blower motor is driven directly using

the onboard PWM output. Multiple blower speeds are

available based upon requirements of the compressor and

electric heat. The blower speeds can be changed either

by the variable speed ECM manual configurations mode

method or by using the Aurora AID Tool directly.

Advanced Hot Water Generator Control
(Domestic Hot Water Option)

An AID Tool selectable temperature limit and

microprocessor control of the process is featured. This will

maximize hot water generation and prevent undesirable

energy use. An alert will occur when the hot water input

temperature is at or above the set point (54.4°C default)

for 30 continuous seconds. This alert will appear as an E15

on the AID Tool and the hot water pump de-energizes. Hot

water pump operations resume on the next compressor

cycle or after 15 minutes of continuous compressor

operation during the current thermostat demand cycle.

Since compressor hot gas temperature is dependent on

The Aurora Advanced VS Control System cont.

Advertising