Unit Startup

Before Powering Unit, Check the Following:

NOTE: Remove and discard the compressor hold down
shipping bolt located at the front of the compressor
mounting bracket.

• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop

pumps wired.

• Condensate line open and correctly pitched.
• Transformer switched to 220V if applicable.
• Black/white and gray/white wires in unit control box

have been removed if auxiliary heat has been installed.

• Dip switches are set correctly.
• Hot water generator pump switch is “OFF” unless piping

is completed and air has been purged.

• Blower rotates freely.
• Blower speed is correct.
• Air filter/cleaner is clean and in position.
• Variable speed drive filter is clean and in place.
• Service/access panels are in place.
• Return air temperature is between 10-26.7°C heating and

15.6-35°C cooling.

• Check air coil cleanliness to ensure optimum

performance. Clean as needed according to maintenance
guidelines. To obtain maximum performance the air coil
should be cleaned before startup. A 10-percent solution
of dishwasher detergent and water is recommended for
both sides of coil, a thorough water rinse should follow.

Powering The Controls

Initial Configuration of the Unit

Before operating the unit, apply power and complete
the following Aurora Startup procedure for the controls
configuration. An AID Tool is required for setup, configuration,
and troubleshooting on the 7 Series Variable Speed system.
AID Tool version 2.01 or greater is preferred.

1. Configure Aurora Screen

a. Confirm AXB is added and communicating.

b. Confirm AOC is added and communicating.

c. Confirm MOC is added and communicating.

d. Confirm EEV2 is added and communicating.

e. Confirm IntelliZone2 is added and communicating

if installed. Set zoning system to OFF.

f. Confirm communicating thermostat is added

and communicating if IntelliZone2 is not installed.

Set thermostat mode to OFF.

NOTE: The AOC and MOC are the two boards that
comprise the VS drive.

2. Aurora Setup Screen

a. ECM Setup for Heating Airflow – select G, low,

high and aux blower speeds as appropriate for the

unit and electric heat.

b. Cooling Airflow % – sets the cooling airflow % from

heating

airflow.

c.

AXB

Setup

i. DHW Enable – Ensure air is purged from

HW system before enabling (remember

the HW switch on the front cabinet)

ii. DHW Setpoint – 54.4°C is the default

but can be changed from 37.8 to 60°C

iii. 7 Series Variable Speed Pump Setup and

Modulating Water Valve Setup – Can be

setup to a range between 5% and 100%.

Defaults are 50% and 100%.

- From the Main Menu of the AID Tool go

to AXB Setup and select “Yes” at the

bottom of the screen to Make Changes

- Set VS Pump Control to MIN

- The pump(s) or water valve should

begin to operate and flow rate is visible

on this screen, it may take several

seconds for flow to stabilize. Adjust the

minimum % until the minimum flow rate

is

achieved.

- Go back to Set VS Pump Control and

select

MAX.

- The pump(s) or water valve should

begin to operate and flow rate is visible

on this screen, it may take several

seconds for flow to stabilize. Adjust the

maximum % until the maximum flow

rate

is

achieved.

-

Press

Enter.

d. Sensor Kit Setup

i. Brine Selection – for HE/HR

capacity

calculation

ii. Flow Meter – activates the flow meter

iii. Select blower energy – PSC or

ECM/5-Speed

ECM

iv.

Activate

energy

option

v. Blower and Aux heat current

sensor

activation

vi. Line Voltage calibration – Voltmeter

required to calibrate line voltage during

heating or cooling. Refer to Line Voltage

Calibration in this manual for more details.

e. Smart Grid Setup – Select action option for utility

received On Peak signal

f. Home Automation 1 and 2 Setup – Select type of

sensor for two home automation inputs.