Refrigerant circuit guideline, Heat of extraction/rejection – WaterFurnace 7 Series User Manual

Page 39

Advertising
background image

39

7 SERIES 50Hz 700A11 INSTALLATION MANUAL

Heat of Extraction/Rejection

Model

L/s

Heat of Extraction (MBtu/h)

L/s

Heat of Rejection (MBtu/h)

-1.1°C

10.0°C

21.1°C

32.2°C

-1.1°C

10.0°C

21.1°C

32.2°C

43.3°C

009

Full Load

5.5

7.7

10.7

13.5

16.0

4.5

12.4

14.2

12.6

12.5

11.8

8.0

7.8

11.0

14.0

16.9

7.0

12.3

14.3

13.8

12.5

11.8

11.5

8.1

11.3

14.6

17.2

9.0

12.4

14.4

13.7

12.5

11.8

012

Full Load

6.5

9.5

13.1

16.1

20.1

5.5

16.4

18.5

16.5

15.7

15.4

10.0

9.6

13.5

17.0

21.3

8.0

16.3

18.5

17.4

15.7

15.4

13.5

9.9

13.8

17.7

21.6

10.5

16.5

18.6

17.3

15.7

15.4

015

Full Load

8.5

11.8

16.0

20.7

25.2

6.5

22.0

22.8

21.8

20.2

18.8

13.0

11.9

16.5

21.7

27.3

10.0

21.9

22.7

21.7

20.1

18.8

17.0

12.3

16.9

22.7

27.7

13.5

22.1

22.8

21.7

20.2

18.8

5/23/13

Symptom

Head

Pressure

Suction

Pressure

Compressor

Amp Draw

Superheat

Subcooling

Air Temp.

Differential

Water Temp.

Differential

Under Charged System (Possible Leak)

Low

Low

Low

High

Low

Low

Low

Over Charged System

High

High

High

Normal

High

Normal/Low

Normal

Low Air Flow Heating

High

High

High

High/Normal

Low

High

Low

Low Air Flow Cooling

Low

Low

Low

Low/Normal

High

High

Low

Low Water Flow Heating

Low/Normal

Low/Normal

Low

Low

High

Low

High

Low Water Flow Cooling

High

High

High

High

Low

Low

High

High Air Flow Heating

Low

Low

Low

Low

High

Low

Low

High Air Flow Cooling

Low

High

Normal

High

Low

Low

Normal

High Water Flow Heating

Normal

Low

Normal

High

Normal

Normal

Low

High Water Flow Cooling

Low

Low

Low

Low

High

Normal

Low

Low Indoor Air Temperature Heating

Low

Low

Low

Normal

High

Normal

Normal/High

Low Indoor Air Temperature Cooling

Low

Low

Low

Normal/Low

High

Low

Low

High Indoor Air Temperature Heating

High

High

High

Normal/High

Normal/Low

Low

Normal

High Indoor Air Temperature Cooling

High

High

High

High

Low

Low

High

Restricted EEV (Check Service Advisory)

High

Low

Normal/Low

High

High

Low

Low

Insufficient Compressor (Possible Bad Valves)

Low

High

Low

High

Normal/High

Low

Low

Scaled Coaxial Heat Exchanger Heating

Low

Low

Low

Normal/Low

High

Low

Low

Scaled Coaxial Heat Exchanger Cooling

High

High

High

Normal/Low

Low

Low

Low

Restricted Filter Drier

Check temperature difference (delta T) across filter drier.

6/1/12

Refrigerant Circuit Guideline

Advertising