ENVISION CONSOLE - 50 HZ INSTALLATION MANUAL

Unit Startup

Electrical Disconnect

Field installed on the optional chassis back plate, the

console disconnect provides a permanent electrical

connection to the main electrical supply branch. Wiring

between the disconnect and the unit chassis is field

supplied and allows the electrical power source to the

chassis to be interrupted for unit servicing.

Non-Fused

Constructed of heavy gauge galvanized steel, the

rocker style disconnect switch provides reliable

electrical control. Wiring pigtails, using 12-gauge wires,

are factory installed to simplify field wiring.

Fused

Similar in construction to the non-fused electrical

disconnect. The fused disconnect is available in

five models with equipment rated fuses to provide

additional circuit protection. The fuses are panel

mounted to allow easy inspection and removal without

removing the cover on the disconnect.

CFD-10 - 10 amp rated fuse

CFD-12 - 12 amp rated fuse

CFD-15 - 15 amp rated fuse

CFD-20 - 20 amp rated fuse

CFD-25 - 25 amp rated fuse

Motorized Outside Air Damper

A field installed motorized outside air damper is available

to allow the introduction of fresh air into the conditioned

space through an outside vent. The damper motor is

powered by 24 volts with a spring-close design in the

event of a power failure. The damper blade and housing are

constructed of aluminum for corrosion resistance and the

blade includes a neoprene gasket to prevent air infiltration

during off cycles. The damper assembly is installed on the

optional chassis back plate and a two-wire low voltage

connection simplifies wiring. A concealed, chassis mounted

rocker switch allows the damper to be disabled

Hydronic Loop Controller for
Boiler/Tower Installations

The hydronic loop controller is a microprocessor based

control panel for control of water loop heat rejector

(tower), heat supplier (boiler), and/or water well pumps

and circulation pumps. Includes audible and visual alarms,

temperature indication, and add-on options of low switches,

remote alarm sensor wells and pump alternator.