Electrical data, Ndw installation manual – WaterFurnace Envision Hydronic (NDW) User Manual

Page 12

Advertising
background image

12

NDW INSTALLATION MANUAL

Figure 1 - Control Box

208 or 230

Volt Switch

(If applicable)

Power Supply

(Field line voltage

connection)

Compressor

Contactor (CC-A)

Compressor

Contactor (CC-B)

Field Low Voltage

Connections

FX10 Control Board

FX10 Expansion Board

Run Capacitor

(Single Phase Only)

Transformer

Compressor

Current Sensors

Optional IntelliStart

TM

Pump Contactor

(CC-P)

Electrical Data

Model

Supply

Circuit

Rated

Voltage

Voltage

Min/Max

Compressor*

Load

Pump

FLA

Source

Pump

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/
HACR

MCC

RLA

LRA

LRA**

100

L1/L2

208-230/60/1

187/253

41.2

26.4

134.0

47.0

-

-

26.4

33.0

50

L3/L4

208-230/60/1

187/253

41.2

26.4

134.0

47.0

4.2

4.2

34.8

41.4

60

Single

208-230/60/3

187/253

24.9

16.0

110.0

66.0

-

-

32.0

36.0

50

Single

460/60/3

414/506

12.1

7.8

52.0

31.0

-

-

15.6

17.6

25

Single

575/60/3

517/633

8.9

5.7

38.9

-

-

-

11.4

12.8

15

120

L1/L2

208-230/60/1

187/253

47.0

30.1

145.0

51.0

-

-

30.1

37.6

60

L3/L4

208-230/60/1

187/253

47.0

30.1

145.0

51.0

4.2

4.2

38.5

46.0

70

Single

208-230/60/3

187/253

28.0

17.3

120.0

72.0

-

-

34.6

38.9

50

Single

460/60/3

414/506

15.0

9.6

70.0

42.0

-

-

19.2

21.6

30

Single

575/60/3

517/633

12.5

8.0

53.0

-

-

-

16.0

18.0

25

150

L1/L2

208-230/60/1

187/253

42.0

26.9

145.0

51.0

-

-

26.9

33.6

60

L3/L4

208-230/60/1

187/253

42.0

26.9

145.0

51.0

4.2

4.2

35.3

42.0

60

Single

208-230/60/3

187/253

35.0

22.4

190.0

114.0

-

-

44.8

50.4

70

Single

460/60/3

414/506

19.0

12.2

87.0

52.0

-

-

24.4

27.5

30

Single

575/60/3

517/633

15.0

9.6

62.0

-

-

-

19.2

21.6

30

180

L1/L2

208-230/60/1

187/253

50.0

32.1

185.0

65.0

-

-

32.1

40.1

70

L3/L4

208-230/60/1

187/253

50.0

32.1

185.0

65.0

4.2

4.2

40.5

48.5

80

Single

208-230/60/3

187/253

39.0

26.0

190.0

114.0

-

-

52.0

58.5

80

Single

460/60/3

414/506

19.0

13.0

100.0

60.0

-

-

26.0

29.3

40

Single

575/60/3

517/633

14.5

9.3

72.0

-

-

-

18.6

20.9

30

3/7/13

HACR circuit breaker in USA only
* Ratings per each compressor - unit supplied with two
** With optional IntelliStart

Advertising