Reference calculations, Legend, Abbreviations and definitions – WaterFurnace Envision Hydronic (NDW) User Manual

Page 26

Advertising
background image

26

NDW INSTALLATION MANUAL

HE

GPM x 500*

Legend

Abbreviations and Definitions

Reference Calculations

Heating Calculations:

Cooling Calculations:

LWT = EWT +

HR

GPM x 500*

LWT = EWT -

NOTE: * When using water. Use 485 for 15% methanol/water or Environol solution.

ELT

= entering load fluid temperature to heat pump

EER

= cooling energy effciency (TC/KW)

LLT

= leaving load fluid temperature from heat pump

PSI

= pressure drop in pounds per square inch

LGPM = load flow in gallons per minute

FT HD = pressure drop in feet of head

LWPD = load heat exchanger water pressure drop

KW =

kilowatt

EST

= entering source fluid temperature to heat pump

HR

= heat rejected in MBTUH

LST

= leaving source fluid temperature from heat pump

TC

= total cooling capacity in MBTUH

SGPM = source flow in gallons per minute

COP

= coefficient of performance (HC/KW x 3.413)

SWPD = source heat exchanger water pressure drop

HC

= heating capacity in MBTUH

HE

= heat of extraction in MBTUH

Advertising