7-7

7.3

Recommissioning

7

Commissioning

2. Switch input "SS1 Activate" or "SS1 SIL3/Reset" to 24 V.

The safety card switches to a "STARTUP" condition. The device and
the safe pulse disabler are tested. The "RUN" LED flashes.

The safety card switches to a "RUN" condition. The "RUN" LED is lit
continuously.

t

1

: At least 2 ms; time during which SS1 Activate or SS1 SIL3/Reset

must have a "0" signal

t

2

: Approx. 2 s, safety card's run-up time

SS1 Activate: Input for safety function SS1

SS1 SIL3/Reset: Input for SIL 3 and reset

STO Acknowledge: Output for feedback from safety function STO

"RUN" LED: System is ready

7.3.2.2

Command "CLRFAULT"

Command "CLRFAULT"

7-

Betrieb_Neustart_CLRFAULT_S1

The safety card can be reset using the "CLRFAULT" command via the
serial interface or fieldbus interface on the servo amplifier.

Prerequisites for using the "CLRFAULT" command

The safety card is in "STOP" condition. The "FAULT" LED is flashing.

Both inputs SS1 Activate and SS1 SIL3/Reset have a "1" signal (24 V).

Alternatively this function can also be assigned to a digital input on the
servo amplifier. Two commands are available:

The command IN1MODE=1, (servo amplifier error reset), activates the
function on digital input DIGITAL-IN1 of the servo amplifier.

The commands INxMODE=30 or INxMODE=33 (run any command
string) activate the function on one of the digital inputs on the servo
amplifier (e.g. IN4MODE=30 on input DIGITAL-IN4).

Funkt_Uebergaenge_Zustaende_IINFO

SS1 SIL3/Reset

1

0

1

0

1

0

1

0

SS1 Activate

STO Acknowledge

LED "RUN"

t2

t

t1

Advertising
This manual is related to the following products:

PMCprimo DriveP.01/AA0/5/0/0/208-480VAC, PMCprimo DriveP.12/AA0/4/0/0/208-480VAC, PMCprimo DriveP.12/AA0/4/P/0/208-480VAC, PMCprimo DriveP.03/AA0/4/0/0/208-480VAC, PMCprimo DriveP.06/AA0/4/0/0/208-480VAC, PMCprimo DriveP.24/ABB/4/0/0/208-480VAC, PMCprimo DriveP.03/AB0/5/0/0/208-480VAC, PMCprimo DriveP.06/AB0/2/0/0/208-480VAC, PMCprimo DriveP.03/AB0/3/0/0/208-480VAC, PMCprimo DriveP.06/AB0/3/0/0/208-480VAC, PMCprimo DriveP.12/AB0/2/0/0/208-480VAC, PMCprimo DriveP.12/ABC/4/P/0/208-480VAC, PMCprimo DriveP.12/AB0/3/0/0/208-480VAC, PMCprimo DriveP.03/AB0/2/0/0/208-480VAC, PMCprimo DriveP.12/AAC/4/0/0/208-480VAC, PMCprimo DriveP.24/AA0/5/0/0/208-480VAC, PMCprimo DriveP.12/AA0/2/0/0/208-480VAC, PMCprotego D.01/000/0/0/2/208-480VAC, PMCprotego D.03/000/0/0/2/208-480VAC, PMCprotego D.06/000/0/0/2/208-480VAC, PMCprotego D.12/000/0/0/2/208-480VAC, PMCprotego D.24/000/0/0/2/208-480VAC, PMCprotego D.12/000/0/P/2/208-480VAC, PMCprotego D.72/000/0/0/2/208-480VAC, PMCprotego D.24/000/0/P/2/208-480VAC, PMCprotego D.48/000/0/0/2/208-480VAC, PMCprotego D.01/200/0/0/2/208-480VAC, PMCprotego D.01/100/0/0/2/208-480VAC, PMCprotego D.01/010/0/0/2/208-480VAC, PMCprotego D.06/010/0/0/2/208-480VAC, PMCprotego D.06/100/0/0/2/208-480VAC, PMCprotego D.06/200/0/0/2/208-480VAC, PMCprotego D.03/010/0/0/2/208-480VAC, PMCprotego D.03/200/0/0/2/208-480VAC, PMCprotego D.03/100/0/0/2/208-480VAC, PMCprotego D.12/010/0/0/2/208-480VAC, PMCprotego D.24/200/0/P/2/208-480VAC, PMCprotego D.12/200/0/0/2/208-480VAC, PMCprotego D.12/100/0/0/2/208-480VAC, PMCprotego D.12/010/0/P/2/208-480VAC, PMCprotego D.12/200/0/P/2/208-480VAC, PMCprotego D.24/100/0/P/2/208-480VAC, PMCprotego D.24/010/0/P/2/208-480VAC, PMCprotego D.12/100/0/P/2/208-480VAC, PMCprotego D.24/200/0/0/2/208-480VAC, PMCprotego D.24/100/0/0/2/208-480VAC, PMCprotego D.24/010/0/0/2/208-480VAC, PMCprotego S1, PMCprotego S2