EDS

M98237501-03-13A

-

Importing or exporting the setup of the EDS system

-

Setup of new devices or slaves

-

Tariff discriminators / calendars

-

Calculated variables

-

System events and alarms

-

Authentication setup

-

Web system security

-

Etc.

Without the PowerStudio Editor tool, the measurement
application cannot be configured to provide new features for
the EDS device. Consequently, the user must install the
software, thus making it possible to integrally configure the
display server and vary the settings of the display, connected
devices, alarms, etc.

4.-

XML instructions

Not only does EDS function as an excellent energy efficiency
manager
for local and multi-point networks, it also has a
default XML requests server that enables it to be easily and
intuitively integrated into a SCADA or remote monitoring
system. The device, via its IP address, attends to GET and
PUT requests that can carry out different functions on the
device.

4.1.- Type of variables

The device has a list of available variables, in accordance
with the device features. The basic code is made up of the
device name and the variables separated by a dot:

-

name.variable

This way the software knows which variable it is and what
device must be asked to find out the value of the variable.

When an incremental variable is discriminated (energy,
impulse meter or similar), the information about the
parameterised discriminator is added to the basic code:

-

name_discriminator@type_time:variable

The discriminable variables are shown in the list with an
asterisk.

4.2.- EDS variables list

If slave devices are provided, the frames sent to EDS are
identified in the same way by name and variable, as shown in
section 4.1.-.

The following table shows the definition of the variables
available in EDS.

Digital inputs

XML - Status Value

XML - Meter Value

Digital Input 1

DI1

C1

Digital input 2

DI2

C2

Digital input 3

DI3

C3

Digital input 4

DI4

C4

Digital input 5

DI5

C5

Digital input 6

DI6

C6

Digital input 7

DI7

C7

Digital input 8

DI8

C8

Digital Output Status

XML - Force Output

Forced Open / Close

Digital Output 1

DO1

0 / 1

Digital Output 2

DO2

0 / 1

Digital Output 3

DO3

0 / 1

Digital Output 4

DO4

0 / 1

Digital Output 5

DO5

0 / 1

Digital Output 6

DO6

0 / 1

Forced Outputs Impulse

XML - Impulse

Forced Impulse

Digital Output 1

DOP1

≠ 0

Digital Output 2

DOP2

≠ 0

Digital Output 3

DOP3

≠ 0

Digital Output 3

DOP4

≠ 0

Digital Output 5

DOP5

≠ 0

Digital Output 6

DOP6

≠ 0

Date and time

XML - Value

Values

Date and Time

VDTTM

Last Server communication

Device status

XML - Impulse

Values

Device status

STATUS.

1

Communication OK

4

Not initialized

18

Port incorrect

34

Comm Errors

66

Device incorrect

4.3.- XML Services

The requests must follow the URI standard (RFC 2396), so
the user of these requests should take this detail into account
when making such calls (especially in cases where the name
of any device contains non-ASCII characters). Take into
account that the length of the request must not under any
circumstance exceed 4000 characters.

4.3.1.- Configured devices request

With this request the XML service returns the list of connected
devices to the EDS energy efficiency manager.

http://x.x.x.x/services/user/devices.xml

http://name_dhcp/services/user/devices.xml

<devices>

<id> ... </id>

<devices>

-

devices: field identifying the XML as a response to the
device list request

-

id: name of each one of the devices

4.3.2.- Information about the device

Request for detailed information about the devices. Each of
devices you want more information, should be include in the
XML sentence ?id=device1?id=device2?

http://x.x.x.x/services/user/deviceInfo.xml

?id=device?

http://dhcp_name/services/user/deviceInfo.xml?id=device
?

<devices>

<device>

<id> ... <id>

<description> ... </description>

<type> ... </type>

<typeDescription> ... </typeDescription>

<var> ... </var>

...

</device>

...

<devices>

-

description: description of device

-

type: device type

-

typeDescription: detailed description of the device

-

var: name of each of the variables of the device; expressed
as name.variable

4.3.3.- Information about the variable

The user can request detailed information about one or more
variables from a device and even make one single request for
the information about all the variables available in the device.

4.3.3.1.- Information about one or more variables

Request for detailed information about one or more variables
of the device (if information is needed about more variables,
link the other requests below with var=device.variable?):

http://x.x.x.x/services/user/varInfo.xml?var=device.variable?

http://name_dhcp/services/user/varInfo.xml?var=device.variab
le?

4.3.3.2.- Information about all the variables

Request for detailed information about all the variables of the
device (if information is needed about more devices, link the
other requests below with id=device?):

http://x.x.x.x/services/user/varInfo.xml?id=device?

http://dhcp_name/services/user/varInfo.xml?id=device?

<varInfo>

<var>

<id> … </id>

<title> ... </title>

<hasValue> T </ hasValue>

<hasLogger> T </ hasLogger>

<sampleMode>… </ sampleMode>

<measureUnits>… </ measureUnits>

<unitsFactor>… </ unitsFactor>

<decimals>… </ decimals>

</ var>

<varInfo>

-

id: variable name in device.variable format

-

title: brief description of the variable

-

hasValue: indicates if it is possible to request the
instantaneous value of the variable (True / False)

-

hasLogger: indicates if it is possible to request the log of
the variable (True / False)

-

sampleMode: type of variable and mode used to group
values

-

measureUnits: variable unit

-

unitsFactor: power of 10 indicating the multiplying factor in
the log file

-

decimals: decimals of the variable

4.3.4.- Instantaneous variable value

The user can request the instantaneous values of one or more
variables, and can even request the information about all the
instantaneous data with just one request.

4.3.4.1.- Instantaneous value of one or more variables

Request for the instantaneous value one or more variables of
the device (if information is needed about more variables, link
the other requests below with var=device.variable?):

http://x.x.x.x/services/user/values.xml?var=device.variable?

http://dhcp_name/services/user/

v

alues.xml?var=device.variab

le?

4.3.4.2.- Instantaneous value of all variables

Request for instantaneous values of all the variables of the
device (if information is needed about more devices, link the
other requests below with id=device?):

http://x.x.x.x/services/user/values.xml?id=device?

http://dhcp_name/services/user/

v

alues.xml?id=device?

<values>

<variable>

<id> … </id>

<value> ... </value>

</ variable>

...

</values>

-

id: identifier of the variable

-

value: value of variable at the time of the request

4.3.5.- Historical data

Request for historical data registry of an incremental variable.
Returns information on one or more variables between the
begin” and “end” dates. Each variable for which information is
required must be included in the request as
?var=device.variable

When only the date is required, the format is DDMMYYYY;
When the date and time are required, the format is
DDMMYYYYHHMMSS. Both the date and the time must be
expressed in UTC (Universal Coordinated Time).

The grouping period can be defined by different criteria:

-

value in seconds (for example 900): value in seconds in
which the data is grouped

-

ALL the data is grouped into a single value

-

AUTO: grouping is automatic with predefined intervals
according to “begin” and “end”

-

FILE: data not grouped. returns the information as
registered in the database

-

if the period parameter does not appear in the request, it is
considered as value 0 and the data is not grouped

http://x.x.x.x/services/user/records.xml?begin=010320110000
00?end=31032011000000?var=device.variable?period=900

http://dhcp_name/services/user/records.xml?begin=01032011
000000?end=31032011000000?var=device.variable?period=
900

<recordGroup>

<period>… </ period>

<record>

<dateTime> ... </ dateTime >

<field>

<id> … </id>

<value>… </value>

</field>

</record>

</recordGroup>

-

recordGroup: field identifying the XML as a response to
the variable register request

-

period: recording period; time between recordings

-

record: identifies each recording (dateTime: date and time
of the sample

-

field: standard recording value (for others consult PS
manual)

-

value: value of variable at the time of the request.

4.3.6.- Historical events file

As this user manual describes, the PowerStudio / Scada
Editor makes it possible to configure events or alarms within
the EDS device and record them in the internal memory.

With the following request, the user can request the historical
events file between the dates defined. Every event that is
requested with a historical events file is defined as
?id=name_event

When only the date is required, the format is DDMMYYYY;
when the date and time are required, the format is
DDMMYYYYHHMMSS. Both the date and the time must be
expressed in Universal Coordinated Time.

http://x.x.x.x/services/user/records.xml?begin=010320110000
00?end=31032011000000?id=event_name