CIRCUTOR EMF-EMB Series User Manual

Page 4

Advertising
background image

----- Static switching modules EM ---------- M98116701-20 Pág: 3

TABLE 2.- Three phase EMB modules

(External fuses must be included)

CODE

OPERATING

VOLTAGE

TYPE

POWER

(kvar)

EXTERNAL

FUSES

TYPE

R41233

380-400V

EMB-40/400

40

80 A

gl

R41236

380-400V

EMB-60/400

60

125 A

gl

R41237

380-400V

EMB-80/400

80

160 A

gl

R41211

220-240 V

EMB-25/230

25

80 A

gl

R41212

220-240 V

EMB-37,5/230

37,5

125 A

gl

R41214

220-240 V

EMB-45/230

45

160 A

gl

Note: Losses are approx. the same as modules EMF of equal size.

2.1 Technical characteristics of EM modules:
Standard supply voltage (power block)

Frequency
Rated power of C step
Overload capability.

Protections

Fuses

dV/dt

Thermostat

di/dt


Max. ambient temperature
Max. heatsink temperature
Protection degree
Dimensions
Mounting distances
Weight

Control of the static switch:

Auxiliary supply at terminals B1-B2

Control method

V A-C open circuit
I A-C closed circuit

400 Vac / 230 Vac (other values up to 690
Vac , on request)
50 / 60 Hz (either)
see table of types
1,5 Inom during 1 minute


NH type (size according to rated current)
RC protection at 1000 V/µs
90 ºC (Opens ENABLE circuit A-C)
100 A/µs ( L= 12µH , not included , must be
mounted in series with the Capacitor)
40 ºC
80 ºC
IP00
See figure 1

10,5 kg.


400 Vac / 230 Vac (Shown in the label)

Potential free contact between terminals A
and C
(see table 5)
20 V cc
Max. 7 mA