CIRCUTOR FAR-Q Series User Manual

Page 3

Advertising
background image

------ Absorption filter ------ User Manual,

M98206701-03-07A ------ Page 2 of 11------

1.- BASIC INSTRUCTIONS

This manual is designed to familiarise the user with operating the FAR-Q power factor
correction and filtering equipment in order to get the best from its features.

FAR-Q hybrid filters are specifically developed for power factor correction on systems
with medium harmonic distortion
. The aim is to improve power factor and at the same
time, to attenuate harmonics. The operating principle consists in correcting power factor
and at the same time absorbing the 5th and 7th harmonics generated by certain loads
so that they do not get into the system or go towards other nearby loads.

Please read this manual carefully before connecting and switching on the
instrument
in order to avoid irreversible damage caused by improper use.

NOTE: So that absorption is effective the hybrid bank must be separate from the other
loads (other lines or users) by a shock reactor or transformer

1.1.- Checking the contents of your package
Please check the following points on receipt of the instrument:

a) The equipment delivered matches your order specifications.
b) Check that the voltage and frequency match the installation's.
c) After unpacking, check that the equipment has not been damaged during

delivery.

d) Check that it is equipped with the following standard items:

- Instruction manual of bank
- Instruction manual of regulator
- Current transformer (not included)

1.2.- Model range of FAR-Q

The range of standard FAR-Q equipment is shown in the following tables.

Table 1.- Standard FAR-Q filters for 50 Hz systems

Q

CODE

TYPE (*)

VOLTAGE STEPS

STEPS x (kvar)

Irms

5

th

7

th

CABINET

(V)

(A) (A) (A)

R7C101 FAR5-Q6-112.5-400

400

3

3 x 37.5

176

60

30

FR6

R7C102 FAR5-Q6-150-400

400

4

4 x 37.5

234

80

40

FR6

R7C103 FAR5-Q6-187.5-400

400

5

5 x 37.5

293

100

50

FR6

R7C104 FAR5-Q6-225-400

400

6

6 x 37.5

351

120

60

FR6

R7C105 FAR5-Q6-262.5-400

400

4

37.5 + (3 x 37.5)

410

140

70

FR6

R7C106 FAR5-Q6-300-400

400

4

4 x 75

469

160

80

FR6

R7C107 FAR5-Q6-337.5-400

400

5

37.5 + (4 x 75)

527

180

90

FR6

R7C108 FAR5-Q6-375-400

400

5

5 x 75

586

200

100

FR6

R7C109 FAR5-Q8-412.5-400

400

6

37.5 + (5 x 75)

644

220

110

FR8

R7C110 FAR5-Q8-450-400

400

6

6 x 75

703

240

120

FR8

R7C111 FAR5-Q8-487.5-400

400

7

37.5 + (6 x 75)

761

260

130

FR8

Advertising